2007-02-14 18:35:58DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 FROM PREVIOUS REVIEW:
  
 A. AS OF 8-25-06 ALL ELECTRICAL, GAS OR
 DIESEL INFORMATION IS REQUIRED WHEN THE
 GEN-COM PERMIT IS APPLIED FOR.
 ****NATURAL GAS INDICATED ON SHT E2.1.
  
 B. OK
  
 C. IF NATURAL GAS OR LP GAS THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRESSED.
  
 3. OK -NATURAL.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****NO RESPONSE, NOT ADDRESSED
  
 7. OK
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS ARE REQUIRED
 AT TIME OF PLAN REVIEW TO VERIFY
 REQUIRED CLEARANCES FOR SERVICE ETC.
 ****THE MAXIMUM BTU LOAD IS NOT SHOWN ON THE MANUF.
 SPECIFICATION SHEETS.
  
 9.N/A
 10. N/A
  
 *************NEW COMMENT*************
  
 1B. SHOW THE LOCATION OF THE GAS METER ON THE PLANS.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]