Plan Review Notes
Plan Review Notes For Permit 06081563
Permit Number 06081563
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-29 08:03:07***** UNSAT 2ND REVIEW *******
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 PLEASE SEE COMMENTS BELOW WHICH ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A *NO* OR *OK* IN FRONT OF
 PREVIOUS NOTE.
  
 **IMPORTANT**
 *PLEASE SEE NEW NOTES NOW ADDED FOR THESE PLANS NOW
 SUBMITTED.
  
  
 1) NOTE:NO, PLEASE SEE PLANS, PERMIT APPLICATION AND
 GENERATOR SPECS DO NOT CORRELATE.
 A) PLEASE SEE PLANS NOW SHOW TWO COMPLETELY DIFFERENT
 SIZES OF GENERATORS (ONE 80KW AND ONE 60KW).
 B) PLEASE SEE SPECS FOR UNIT ARE FOR A NATURAL GAS UNIT
 AND PLANS AND APPLICATION IS FOR DIESEL.
 C) PLEASE SEE FUEL TANK IS FOR A DIESEL UNIT.
 D) PLEASE SEE PLANS CALL FOR NATURAL GAS ALSO??
 E) PLEASE PROVIDE DOCUMENTATION ON THIS LEGALLY
 REQUIRED STANDBY UNIT AND HOW MUCH ON SITE FUEL IS
 REQUIRED AND FUEL CONSUMPTION ON THIS UNIT ONCE ALL HAS
 BEEN COORDINATED
  
 ** PLEASE CORRELATE ALL AND CORRECT PLANS.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE CORRELATE PLANS, SPECS AND APPLICATION. PLEASE
 SEE APPLICATION IS FOR A DIESEL GEN, SPECS FOR A DIESEL
 AND SPEC FOR NAT GAS. PLEASE SEE PLANS DO NOT INDICATE
 WHICH ONE OF EITHER.
 PLEASE KNOW, AS BEING LEGALLY REQUIRED, PLEASE SEE
 701.11B3
  
 2) NOTE: OK.
  
 3) NOTE:NO, PLEASE KNOW AS THE UNIT IS STILL IN
 QUESTION, THE SET BACKS CAN NOT BE CONFIRMED AT THIS
 TIME. PLEASE ALSO SEE THE MANUFACTURES SPECS/CUT SHEETS
 DO NOT CORRELATE SO THE CORRECT SET BACKS CAN NOT BE
 DETERMINED AT THIS TIME. PLEASE SEE THE SPEC/CUT SHEETS
 FROM THE MANUFACTURE DO NOT CONTAIN ANY INFORMATION AS
 TO THEIR MINIMUM REQUIRED CLEARANCES. PLEASE KNOW BASED
 ON THE MANUFACTURE AND TYPE OF UNIT BEING INSTALLED,
 THIS WILL VARY MANY TIMES FROM 3FT TO 5FT OR MORE.
 PLEASE SEE AS DOCUMENTATION IN PLANS CALLS FOR WALLS
 ETC TO BE INSTALLED AND NOT ON PLANS THIS CAN NOT BE
 CONFIRMED AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE SEE PLANS DO NOT SHOW ALL SET BACKS AND
 DISTANCES FROM SURROUNDING BUILDINGS FOR MINIMUM
 CLEARANCES FROM WINDOWS STRUCTURES ETC.
 PLEASE BE SURE THE MIN CLEARANCES FROM ALL CLEARANCES
 ARE SHOWN/ AND STATED FROM MANUFACTURE. PLEASE SEE A
 MIN OF 5FT FROM BUILDING FOR CLEARANCE MAY BE REQUIRED
 DEPENDING ON MANUFACTURE. 10FT MAY BE REQUIRED FOR ANY
 OPENINGS INTO BUILDING FOR MECHANICAL VENTILATION,
 PLEASE SEE 3FT IS MIN FOR ELECTRICAL/WORKING
 CLEARANCE.
 PLEASE SEE 110.26, 90.7, 110.3 AND NOTES FROM OTHER
 TRADES.
  
 4) NOTE: NO, SAME NOTE FOR ANY VERTICAL RUNS.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE SEE HEIGHT OF BUILDING IS NOT SHOWN; PLEASE SEE
 300.19 FOR STRAIN RELIEF REQUIRED FOR CONDUCTORS ON
 VERTICAL RUNS.
  
 5) NOTE:NO, PLEASE SEE THE PLANS NOW INDICATE A NEW
 DISCONNECT HOWEVER NO INFORMATION FOR LOCATION AND
 WHERE THIS IS SHOWN ON PLAN OVER VIEW IN COMPARISON TO
 THE MAIN ELECTRICAL ROOM.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE SEE MISSING MEANS OF DISCONNECT FOR FEEDERS FROM
 GEN TO BUILDING. PLEASE SHOW LOCATION OF ALL EXISTING
 MEANS OF DISCONNECTS FOR MAIN BLDG.
 PLEASE SEE 225.34, 230.72.
 225.31-225.39,701.11B5, ALSO 110.27
  
 6) NOTE: NO, NO INFORMATION IS BEING SHOWN FOR ROUTING
 OF THESE CONDUITS.
 ARE THERE ANY CONDUITS BEING RUN IN BUILDING?
 ARE THERE ANY CONDUITS RUN IN EGRESS STAIRS OR ELEVATOR
 EQUIPMENT ROOMS?
 ** PLEASE PROVIDE THIS INFORMATION.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE SHOW HOW AND WHERE CONDUITS FOR FEEDERS ARE
 BEING RUN IN
 BLDG. (PLEASE KNOW, NO CONDUITS ARE PERMITTED IN
 EXIT/EGRESS STAIRS.
 FBC 106.1.2
  
 7) NOTE: OK
  
 8) NOTE: NO, THE APPLIED AMOUNT WHICH WAS INCREASED TO
 $25K WAS INCREASED TO $35K BASED ON THE PLANS SUBMITTED
 AND THE SCOPE OF WORK IN DOCUMENTATION.
 PLEASE KNOW BASED ON THE PLANS, DOCUMENTATION NOW
 PROVIDED ADDITIONAL FEES OF $222.00 IS NOW OWED.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE KNOW, DEPENDING ON THE TOTAL SCOPE OF WORK THE
 APPLIED VALUE IS REQUIRED TO BASED ON ALL LABOR AND
 MATERIALS. FBC 108.3. (EVEN OF ANY EQUIPMENT/MATERIALS
 ARE OWNER SUPPLIED.
  
  
 **** NEW NOTES ****
  
 9) NOTE: PLEASE SEE PAPER WORK AND DOCUMENTATION NOW
 SUBMITTED WHICH STATES NEW MASONRY WALLS ARE TO BE
 INSTALLED, HOWEVER NO PLANS, SET BACKS ETC WERE
 SUBMITTED TO SHOW SCOPE OF WORK. PLEASE KNOW THE VALUE
 MAY ALSO BE ADJUSTED.
  
 10) NOTE: PLEASE SEE LETTERS MENTIONS THIS JOB LOCATION
 TO BE IN PALM BEACH COUNTY JURISDICTION; HOWEVER THIS
 IS IN THE CITY OF WEST PALM BEACH.
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 13) NOTE: PLEASE KNOW THAT BASED ON THE COORDINATION OF
 PLANS AND SPECS SUBMITTED, THERE MAY BE COMMENTS ONCE
 AGAIN ON THE FOLLOWING REVIEW WHICH HAS NOT YET BEEN
 MADE AT THIS TIME.
  
 14) NOTE: PLEASE KNOW SINCE THIS IS NOW BEING STATED IN
 A FLOOD ZONE, A CERTIFIED ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE FINAL. PLEASE SUBMIT TWO COPIES, ONE
 WILL BE RETAINED AND PLACED IN FILE AND THE OTHER WILL
 BE STAMPED FOR JOBSITE FOR FINAL INSPECTION. THIS IS
 NOT REQUIRED AT THIS TIME AND IS ONLY BEING NOTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-28 19:02:142007-01-28 19:02:14
  
 IN ELEC FOR REVIEW
 NOTES TO FOLLOW. WILL BE IN *F* STATUS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved