Plan Review Notes
Plan Review Notes For Permit 06081563
Permit Number 06081563
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-27 00:00:00***** UNSAT *******
  
 1) NOTE: PLEASE CORRELATE PLANS, SPECS
 AND APPLICATION. PLEASE SEE APPLICATION
 IS FOR A DIESEL GEN, SPECS FOR A DIESEL
 AND SPEC FOR NAT GAS. PLEASE SEE PLANS
 DO NOT INDICATE WHICH ONE OF EITHER.
 PLEASE KNOW, AS BEING LEGALLY REQUIRED,
 PLEASE SEE 701.11B3
  
 2) NOTE: PLEASE SEE PLANS SHOULD REFLECT
 ALL CURRRENTS CODES IN EFFECT.
 2004 FBC, 2002 NFPA-70, 2002 NFPA-110,
 2003 NFPA-101 (MIN).
  
 3) NOTE: PLEASE SEE PLANS DO NOT SHOW
 ALL SET BACKS AND DISTANCES FROM
 SURROUNDING BUILDINGS FOR MINIMUM
 CLEARENCES FROM WINDOWS STRUCTURES ETC.
 PLEASE BE SURE THE MIN CLEARENCES FRO
 ALL CLEARENCES ARE SHOWN/ AND STATD FROM MANUFACTURE.
 PLEASE SEE A MIN OF 5FT
 FROM BUILDING FOR CLEARNCE MAY BE
 REQUIRED DEPENDING ON MANUFACTURE. 10FT
 MAY BE REQUIRED FOR ANY OPENINGS INTO
 BUIDLIGN FOR MECHANICAL VENTILATION,
 PLEASE SEE 3FT IS MIN FOR
 ELECTRICAL/WORKING CLEARENCE.
 PLEASE SEE 110.26,90.7,110.3 AND NOTES
 FROM OTHER TRADES.
  
 4) NOTE: PLEASE SEE HEIGHT OF BUILDING
 IS NOT SHOWN, PLEASE SEE 300.19 FOR
 STRAIN RELIEF REQUIRED FOR CONDUCTORS ON
 VERTICAL RUNS.
  
 5) NOTE: PLEASE SEE MISSING MEANS OF
 DISCONNECT FOR FEEDERS FROM GEN TO
 BUILDING. PLEASE SHOW LOCATION OF ALL
 EIXSTING MEANS OF DISCONNECTS FOR MAIN
 BLDG.
 PLEASE SEE 225.34, 230.72.
 225.31-225.39,701.11B5, ALSO 110.27
  
 6) NOTE: PLEASE SHOW HOW AND WHERE
 CONDUITS FOR FEEDERS ARE BEING RUN IN
 BLDG. (PLEASE KNOW, NO CONDUITS ARE
 PERMITTED IN EXIT/EGRESS STAIRS.
 FBC 106.1.2
  
 7) NOTE: PLEASE PROVIDE INFORMATION FOR
 LOADS ON PROPOSED GENERATOR.
 701.6, 220
  
 8) NOTE: PLEASE KNOW, DEPENDING ON THE
 TOTAL SCOPE OF WORK THE APPLIED VALUE IS
 REQUIRED TO BASED ON ALL LABOUR AND
 MATERIALS. FBC 108.3. (EVEN OF ANY EQUIPMENT/MATERIALS
 ARE OWNER SUPPLIED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  