| 2006-08-27 00:00:00 | ***** UNSAT ******* |
| | |
| | 1) NOTE: PLEASE CORRELATE PLANS, SPECS |
| | AND APPLICATION. PLEASE SEE APPLICATION |
| | IS FOR A DIESEL GEN, SPECS FOR A DIESEL |
| | AND SPEC FOR NAT GAS. PLEASE SEE PLANS |
| | DO NOT INDICATE WHICH ONE OF EITHER. |
| | PLEASE KNOW, AS BEING LEGALLY REQUIRED, |
| | PLEASE SEE 701.11B3 |
| | |
| | 2) NOTE: PLEASE SEE PLANS SHOULD REFLECT |
| | ALL CURRRENTS CODES IN EFFECT. |
| | 2004 FBC, 2002 NFPA-70, 2002 NFPA-110, |
| | 2003 NFPA-101 (MIN). |
| | |
| | 3) NOTE: PLEASE SEE PLANS DO NOT SHOW |
| | ALL SET BACKS AND DISTANCES FROM |
| | SURROUNDING BUILDINGS FOR MINIMUM |
| | CLEARENCES FROM WINDOWS STRUCTURES ETC. |
| | PLEASE BE SURE THE MIN CLEARENCES FRO |
| | ALL CLEARENCES ARE SHOWN/ AND STATD FROM MANUFACTURE. |
| | PLEASE SEE A MIN OF 5FT |
| | FROM BUILDING FOR CLEARNCE MAY BE |
| | REQUIRED DEPENDING ON MANUFACTURE. 10FT |
| | MAY BE REQUIRED FOR ANY OPENINGS INTO |
| | BUIDLIGN FOR MECHANICAL VENTILATION, |
| | PLEASE SEE 3FT IS MIN FOR |
| | ELECTRICAL/WORKING CLEARENCE. |
| | PLEASE SEE 110.26,90.7,110.3 AND NOTES |
| | FROM OTHER TRADES. |
| | |
| | 4) NOTE: PLEASE SEE HEIGHT OF BUILDING |
| | IS NOT SHOWN, PLEASE SEE 300.19 FOR |
| | STRAIN RELIEF REQUIRED FOR CONDUCTORS ON |
| | VERTICAL RUNS. |
| | |
| | 5) NOTE: PLEASE SEE MISSING MEANS OF |
| | DISCONNECT FOR FEEDERS FROM GEN TO |
| | BUILDING. PLEASE SHOW LOCATION OF ALL |
| | EIXSTING MEANS OF DISCONNECTS FOR MAIN |
| | BLDG. |
| | PLEASE SEE 225.34, 230.72. |
| | 225.31-225.39,701.11B5, ALSO 110.27 |
| | |
| | 6) NOTE: PLEASE SHOW HOW AND WHERE |
| | CONDUITS FOR FEEDERS ARE BEING RUN IN |
| | BLDG. (PLEASE KNOW, NO CONDUITS ARE |
| | PERMITTED IN EXIT/EGRESS STAIRS. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE PROVIDE INFORMATION FOR |
| | LOADS ON PROPOSED GENERATOR. |
| | 701.6, 220 |
| | |
| | 8) NOTE: PLEASE KNOW, DEPENDING ON THE |
| | TOTAL SCOPE OF WORK THE APPLIED VALUE IS |
| | REQUIRED TO BASED ON ALL LABOUR AND |
| | MATERIALS. FBC 108.3. (EVEN OF ANY EQUIPMENT/MATERIALS |
| | ARE OWNER SUPPLIED. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |