Plan Review Notes
Plan Review Notes For Permit 06081563
Permit Number 06081563
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-28 00:00:00DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE EQUIPMENT IS LOACTED IN AN "A8"
 FLOOD ZONE AND ELEVATION CERTIFICATE
 WILL BE REQUIRED. BASE FLOOD ELEVATION
 IS 16 FEET PLUS THE .5 FEET REQUIRED BY
 CITY ORDINANCE.
  
 3) PROVIDE DETAILS OF THE SLAB THAT WILL
 SUPPORT THE GENERATOR. INDICATE HOW THE
 GENERATOR WILL BE ANCHORED TO THE SLAB.
 SHOW COMPLIANCE WITH FBC 1609.1.3 FOR
 ANCHORAGE AGAINST OVERTURNING, UPLIFT
 AND SLIDING. PROVIDE PLANS ENOUGH TO
 VERIFY LOCATION OF GENERATOR VERSES
 BUILDING OPENINGS WINDOWS, DOORS OR
 SOFFIT TYPE VENTS, ETC.
 GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BE USED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  