| 2006-08-28 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE EQUIPMENT IS LOACTED IN AN "A8" |
| | FLOOD ZONE AND ELEVATION CERTIFICATE |
| | WILL BE REQUIRED. BASE FLOOD ELEVATION |
| | IS 16 FEET PLUS THE .5 FEET REQUIRED BY |
| | CITY ORDINANCE. |
| | |
| | 3) PROVIDE DETAILS OF THE SLAB THAT WILL |
| | SUPPORT THE GENERATOR. INDICATE HOW THE |
| | GENERATOR WILL BE ANCHORED TO THE SLAB. |
| | SHOW COMPLIANCE WITH FBC 1609.1.3 FOR |
| | ANCHORAGE AGAINST OVERTURNING, UPLIFT |
| | AND SLIDING. PROVIDE PLANS ENOUGH TO |
| | VERIFY LOCATION OF GENERATOR VERSES |
| | BUILDING OPENINGS WINDOWS, DOORS OR |
| | SOFFIT TYPE VENTS, ETC. |
| | GENERATOR SLAB & ANCHOR REQUIREMENT |
| | PLEASE PROVIDE SIZE OF GENERATOR(WXL), |
| | PLUS PROVIDE PLANS WITH THE INFORMATION |
| | DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE |
| | THE DEVICE REQUIRES WITHOUT LOAD |
| | REDUCTION. |
| | SECOND, PROVIDE INFORMATION ON THE |
| | SLAB, THICKNESS, WIDTH AND LENGTH, IF |
| | WIREMESH, FIBER MESH OR IF STEEL REBAR |
| | WILL BE USED. |
| | THE NEW SLAB AND HOLD DOWN DETAILS: |
| | 104.2.1* ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |