| Plan Review Notes For Permit 06081557 |
| Permit Number |
06081557 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-03 00:00:00 | | | | | | | DENIED | | | | | | 1) CIY OF WEST PALM BEACH REQUIRES 2 | | | COPIES OF THE FLORIDA STATE PRODUCT | | | APPROVAL COVER SHEETS AND THE ASSOCIATED | | | DRAWINGS, EVALUATION REPORTS OR | | | MIAMI-DADE NOA THAT WAS USED FOR THE | | | STATE APPROVAL. PGT FL# 243-R3 AND A | | | NREVISED MIAMI-DADE NOA # 03-1105.01 | | | | | | 2) PROVIDE GLASS TYPE BOTH WERE MARKED | | | IN THE DRAWINGS AND THE DESIGN PRESSURES | | | ARE DIFFERENT FOR EACH | | | | | | 3) THE MAX ALLOWABLE SIZE IN SQ. FT. FOR | | | THE IMPACT RESISTANT WINDOWS IS 32 SQ. | | | FT. THEREFORE THE OPENING SIZES LISTED | | | ARE INCORRECT UNLESS THEIR IS MORE THAN | | | ONE WINDOW PER OPENING . IF THIS IS THE | | | CASE PLEASE GIVE THE WINDOW SIZES FOR | | | EACH OPENING AND PROVIDE A PRODUCT | | | APPROVAL FOR THE MULLIONS. | | | | | | 4) THE DESIGN PRESSURES STATED ARE | | | INCORRECT THEY SHALL BE BASED ON THE | | | EFFECTIVE WIND AREA OF THE WINDOW AND | | | NONE ARE LARGER THAN 50 SQ. FT.IF USING | | | THE CODE BOOK TABLES, SEE NOTE 1 AND | | | ALSO SPECIFY IF OPENING IS IN ZONE 4 OR | | | 5 | | | | | | ADRIAN MORSE | | | BLDG PLAN REVIEW | | | 561-805-6716 | | | | | | |
|