Plan Review Notes
Plan Review Notes For Permit 06081555
Permit Number 06081555
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-27 00:00:00***** UNSAT *****
  
 1) NOTE: PLEASE VERIFY IF THERE ARE ANY
 EXISTING ORNEW ELECTRICAL BEING
 PROVIDE TO FEED NEW TENANTS/SPACES.
 PLEASE KNOW MIN EGRESS LIGHTING IS GOING
 TO BE REQUIRED FOR NEW SPACES AND EGRESS
 HALLS.
 THIS MIN LIGHTING EVEN IF FED FROM
 EXISTING HOUSE SERVICE IS REQUIRED AT
 THIS TIME.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS FOR
 THIS.
 NFPA-101 2003, 7.8, 7.9
 PLEASE SEE 700.12E FOR CIRCUITING PER
 NFPA-70 2002
  
 2) NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCKS PER
 FAC 61G15-23.002 AND FS 471.023.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
 3) NOTE: PLEASE SEE PLANS MAY NOT
 CONTAIN HAND WRITTEN INFORMATION OR
 WHITE-OUT OF ANY KIND ON PLANS WHICH ARE
 SIGNED, DATED AND SEALED BY AN ENGINEER.
 FS 471.023
  
 4) NOTE: PLEASE SEE PLANS APPEAR TO BE
 SIGNED WITH SOME SORTOF INITIAL(S). IF
 INDEEDTHE IS THE LEGAL SIGNATURE OF
 THE ENGINEER PLEASE SUBMIT A LETTER
 WHICH STATES THIS AS LEGAL SIGNATURE,
 LETTER TO BE SIGNED, DATED AND SEALED
 ALSO IS REQUIRED TO BE NOTARIZED
 PROPERLY PER FS 117.05
  
 5) NOTE: PLEASE BE SURE PLANS REFLECT
 ALL THE CURRENT CODE S IN EFFECT FOR
 DESIGN.
 2004 FBC , 2002 NFPA-70, 2003 NFPA-101
 (MIN) PLEASE SEE ANY OHER CODES WHICH
 MAY BE REQUIRED FROM OTHER
 TRADES/REVIEWS.
  
 6) NOTE: PLEASE SEE THE NOTICE OF
 COMMENCMENT SUBMITTED WAS NOT RECORDED.
 PLEASE SEE FS 713.13(2).
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  