Plan Review Notes
Plan Review Notes For Permit 06081555
Permit Number 06081555
Review Stop B
Sequence Number 1
Notes
Date Text
2006-09-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06081555
 ADD: 255 EVERNIA ST
 UNITS MU1-MU4
 CONT: INPROSFL, INC
 TEL: (954)2020500
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 106.1.2* ADDITIONAL INFORMATION
 REQUIRED. IT APPEARS THAT A PERMIT TO
 SUBDIVIDE A SINGLE SPACE INTO 4 SEPERATE
 TENANT SPACES HAS BEEN APPLIED FOR.
 SINCE THESE ARE CONDO UNITS WHICH HAVE
 SEPERATE PROPERTY CONTROL NUMBERS &
 OWNERS, SEPERATE PERMIT APPLICATIONS
 SHALL BE APPLIED FOR, FOR EACH UNIT.
 NOTE ALSO THE PERMIT APPLICATION
 APPLIED FOR NEEDS TO CORRECT THE
 PROPERTY CONTROL NUMBER FOR THE UNIT FOR
 WHICH IT WILL APPLY FOR PERMIT.
  
 3) SINCE EACH UNIT WILL REQUIRE ITS OWN
 PERMIT APPLICATION,A NOTICE OF
 COMMENCEMENT WILL ALSO NEED TO BE
 RECORDED AT THE CLERK OF THE COURT.
 FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 4) BROMLEY COOK ENGINEERING, INC. IS
 MISSING THEIR CERTIFICATE OF
 AUTHORIZATION:471.023 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ENGINEER PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 5) WILLIAM D. COOK P.E. PLEASE PROVIDE A
 NOTIRIZED LETTER TO THIS OFFICE STATING
 AND SIGNING YOUR LEGAL SIGNATURE. THIS
 LEGAL SIGNATURE TO BE USED ON PLANS.
 FL S S 117.05.
  
 6) PLANS ARE MISSING:
 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 7) WIND REQUIREMENTS MISSING:
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 8) SHEET S-1 INDICATES BEHIND THE NEWLY
 CREATED SUITES, A COMMON AREA, WHAT IS
 THIS AREA TO BE USED FOR?
  
 9) THE LEFT OF THE SHEET S-1 A STAIR
 ENCLOSURE IS PRESENT, THIS APPEARS TO BE
  
 ONE OF THE EGRESS STAIRS REQUIRING A 2HR
 RATED ASSEMBLY TO THE EXTERIOR OF THE
 BUILDING, PLANS ONLY INDICATE A 1 HR
 TENANT SEPERATION.1019.1.
  
 10) STOREFRONT PLANS SHEET 1/3 HAVE
 WHITE OUT AND HAND WRITTEN INFORMATION
 ON PLANS. 104.2.1.3 THE BUILDING
 OFFICIAL MAY SET STANDARDS THROUGH
 DEPARTMENTAL POLICY STANDARDS FOR PLANS
 AND SPRCIFICA TIONS. "NO WHITE OUT".
  
 11) INDICATE ON THE PERMIT APPLICATION
 IF THESE PLANS ARE FOR TENANT SEPERATION
 WALLS, NOT A TENANT BUILD OUT.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13)W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026