Plan Review Notes
Plan Review Notes For Permit 06081546
Permit Number 06081546
Review Stop E
Sequence Number 4
Notes
Date Text
2007-02-03 14:14:08*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE RISER HAS NOW BEEN REVISED TO ADD
 AN ADDITIONAL METER AND SERVICE TO THE SAME TENANT.
 THIS NEEDS TO BE CLARIFIED.PLEASE PROVIDE LOAD
 CALCULATIONS FOR THE ADDITION OF LOADS TO THE EXISTING
 SERVICE GUTTER. PLEASE SEE THE PREVIOUS RISER SHOWED A
 NEW FEED FROM THE EXISTING 600A GUTTER TO NEW GUTTER,
 YET THIS RISER SHOWS THIS NOW AS EXISTING?
 PLEASE SEE THE SAME TENANT IS NOW SHOWING TWO METERS
 FOR THE SAME SPACE?220, 220.35 ETC
  
 ** PLEASE CLARIFY AND REVISE THE ABOVE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  