Plan Review Notes
Plan Review Notes For Permit 06081546
Permit Number 06081546
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE
 FOLLOWING INFORMATION IS REQUIRED IN THE
 TITLE BLOCK:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 FAS 61G1-16.004 & FS 481.219 - 481.2055.
  
 2. SEAL SHALL BE SIGNED AND DATED. NO
 DATE IS ON SEAL, AND IT APPEARS TO BE
 INITIALS. IF THIS IS YOUR LEGAL
 SIGNATURE, THEN A NOTORIZED LETTER
 INDICATING YOUR LEGAL SIGNATURE IS
 REQUIRED FOR OUR FILES. FAC
 61G1-16.004(5) & FS 481.2055.
  
 3. SHT BETWEEN A6.01 & A7.01, (NOT
 NUMBERED), DETAIL #2 ELEVATION COMMONS
 EAST. SHOW THE FOLLOWING INFORMATION:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED)
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 4. SHT P1.02 WATER PIPING ISOMETRIC.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" AND NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS. - WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE ICE MAKER AND THE
 DISH WASHER PER SECTION 604.9.
  
 5. SHT P1.02 WATER PIPING ISOMETRIC. A
 FULL OPEN VALVE IS REQUIRED ON THE TOP
 OF ALL WATER DOWN-FEED PIPES. SECTION
 606.1(4).
  
 6. SHT P1.02 GENERAL NOTES #1. AIR
 CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE. SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]