| 2006-09-08 00:00:00 | ********* UNSAT ********** |
| | |
| | 1) NOTE: PLEASE SEE MISSING INFORMATION |
| | ON TITLE BLOCKS REQUIRED FOR THE |
| | ARCHITECTURAL FIRM. PLEASE SEE MISSING |
| | CERTIFICATE OF AUTHORIZATION NUMBER, |
| | PRINTED NAME, LICENSE #S', ADDRESS FOR |
| | FIRM, ETC. PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G1-16.004 AND |
| | FLORIDA STATUES 481.221, AND FS 481.219. |
| | THIS IS REQUIRED FOR ALL SHEETS CONTAIN |
| | SAID ARCHITECTURAL TITLE BLOCK AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE LIST THE LATEST ADOPTED |
| | EDITION OF NFPA-75 (2002). |
| | |
| | 3) NOTE: PLEASE SEE COLOR CODING FOR |
| | 277/480V SHALL BE AS FOLLOWS. BROWN, |
| | PURPLE, YELLOW. |
| | PLEASE KNOW, "ORANGE" AS INDICATED IS |
| | REQUIRED FOR 120/240V OPEN DELTA, FOR |
| | SYSTEMS WITH A HIGH-LEG. |
| | THE NEC DOES NOT INCLUDE COLOR CODING |
| | FOR 277/480 AND SUCH SYSTEMS LOCATED IN |
| | THIS JURISDICTION HAVE PREVIOUSLY BEEN |
| | COLOR CODED PER ABOVE PER LOCAL |
| | AMENDMENTS. 90.4, 215.5 |
| | |
| | 4) NOTE: PLEASE SEE MISSING REQUIRED |
| | LIGHTING CONTROLS PER FBC 2004 CHAPTER |
| | 13. 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE ALSO PROVIDE ENERGY CALCULATIONS |
| | AND LIGHTING POWER DENSITIES AS |
| | REQUIRED. |
| | 113-415.1.AB.1, 13-415.2.ABC.1,; TABLES |
| | 415.2.C.1 AND 415.2.B.1. |
| | PLEASE SHOW AND INDICATE SCHEDULING, |
| | TYPES AND LOCATIONS FOR CONTROLS AND |
| | OVER RIDES DEVICES. PLEASE INDICATE THE |
| | AMOUNT OF TIME ON OVER RIDE DEVICES. |
| | (TIMER TYPE4HRS MAX, OCCUPANCY SENSOR |
| | TYPE 30 MINS MAX) ETC. |
| | ETC. AS NO SYSTEM IS BEING SHOWN AT THIS |
| | TIME, REVIEW OF SUCH SYSTEM FOR CODE |
| | COMPLIANCE CAN NOT BE DONE. |
| | |
| | 5) NOTE: PLEASE SEE COMPLETE VALUATION |
| | FOR COMPLETE SCOPE OF WORK AS INDICATED |
| | ON PLANS SAHLL INCLUDE ALL LABOUR AND |
| | MATERIALS WHETHER OR NOT AN EUIPMENT/ |
| | MATERIALS ARE OWNER SUPPLIED. FBC 108.3 |
| | PLEASE SEE APPLIED VALUE SEEMS LOW FOR |
| | SCOPE SHOWN AND NEW EQUIPMENT BEING |
| | INDICATED. PLEASE KNOW, IF THE VALUE IS |
| | NOT ADJUSTED, ONE WILL BE ADJUSTED PER |
| | 'MARSHALL'S & SWIFT" GUIDES AS ADOPTED |
| | ON THE FBC. |
| | |
| | 6) NOTE: PLEASE INCLUDE AND SUBMIT |
| | MANUFACTURES SPECS/CUT SHEETS FOR ALL |
| | THE NEW UPS/ LEIBERT SYSTEM EQUIPMENT. |
| | PLEASE BE SURE THE SPECS INDICATE A |
| | LISTING FROM A NRTL. |
| | |
| | 7) NOTE: PLEASE SEE NFPA-75, AND |
| | NFPA-70, 645 AS THE MDF ROOM SEEMS TO |
| | CLEARLY INDICATE AN "IT" ROOM. PLEASE |
| | SEE MECHANICAL REQUIREMENTS FOR RATED |
| | DMAPERS, SD'S. |
| | PLEASE SEE AN EPO IS BEING SHOWN, |
| | HOWEVER HOW THIS IS BEIGN TIED IN AND |
| | SHUNTING THE POWER COMING FROM "L2A1, |
| | L2A2 AND URL" IS UNCLEAR AT THIS TIME. |
| | PLEASE SEE NO MENTION IN THESE PANELS |
| | COULD BE LCOATED FOR SHUNT AND |
| | DISCONNECTING MEANS. |
| | 645.1-.16 |
| | |
| | 8) NOTE: PLEASE SEE FIRE REVIEW COMMENTS |
| | AS ACCESS CONTROL SYSTEM(S) NEEDS TO BE |
| | VERIFIED. PLEASE SEE NFPA-101 AS A FAIL |
| | SAFE MODE/ BACK-UP IS REQUIRED SO THAT |
| | MEANS OF EGRESS MAY NOT BE IMPEDED. |
| | 7.2.1.5 |
| | PLEASE SEE THAT SYSTEM AS SHOWN IS NOT |
| | CLEAR OF CODE COMPLIANCE AT THIS TIME. |
| | PLEASE SEE THAT ANY COMMENTS FORM FIRE |
| | REVIEW WILL BE REQUIRED TO BE ADJUSTED |
| | ON ELECTRICAL PLANS. |
| | |
| | 9) NOTE: PLEASE COMPLETE PANEL SCHEDULES |
| | INDICATING ALL CONDUCTOR SIZES AND |
| | CORRELATING WIHT THE OCP AS SHOWN. |
| | PLEASE SEE 240.4,310.16,408.4. |
| | THIS IS REQUIRED AT THIS TIME. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SUBMIT COMPLETED LOAD |
| | CALCULATIONS PER 220.3,220.10,220.11, |
| | 210.13, ETC AND PLEASE SHOW ALL |
| | CONTINUOUS LOADS AT 125% 215.3,230.42 |
| | ETC. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |