Plan Review Notes
Plan Review Notes For Permit 06081546
Permit Number 06081546
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-08 00:00:00********* UNSAT **********
  
 1) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS REQUIRED FOR THE
 ARCHITECTURAL FIRM. PLEASE SEE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER,
 PRINTED NAME, LICENSE #S', ADDRESS FOR
 FIRM, ETC. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AND
 FLORIDA STATUES 481.221, AND FS 481.219.
 THIS IS REQUIRED FOR ALL SHEETS CONTAIN
 SAID ARCHITECTURAL TITLE BLOCK AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE LIST THE LATEST ADOPTED
 EDITION OF NFPA-75 (2002).
  
 3) NOTE: PLEASE SEE COLOR CODING FOR
 277/480V SHALL BE AS FOLLOWS. BROWN,
 PURPLE, YELLOW.
 PLEASE KNOW, "ORANGE" AS INDICATED IS
 REQUIRED FOR 120/240V OPEN DELTA, FOR
 SYSTEMS WITH A HIGH-LEG.
 THE NEC DOES NOT INCLUDE COLOR CODING
 FOR 277/480 AND SUCH SYSTEMS LOCATED IN
 THIS JURISDICTION HAVE PREVIOUSLY BEEN
 COLOR CODED PER ABOVE PER LOCAL
 AMENDMENTS. 90.4, 215.5
  
 4) NOTE: PLEASE SEE MISSING REQUIRED
 LIGHTING CONTROLS PER FBC 2004 CHAPTER
 13. 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE ALSO PROVIDE ENERGY CALCULATIONS
 AND LIGHTING POWER DENSITIES AS
 REQUIRED.
 113-415.1.AB.1, 13-415.2.ABC.1,; TABLES
 415.2.C.1 AND 415.2.B.1.
 PLEASE SHOW AND INDICATE SCHEDULING,
 TYPES AND LOCATIONS FOR CONTROLS AND
 OVER RIDES DEVICES. PLEASE INDICATE THE
 AMOUNT OF TIME ON OVER RIDE DEVICES.
 (TIMER TYPE4HRS MAX, OCCUPANCY SENSOR
 TYPE 30 MINS MAX) ETC.
 ETC. AS NO SYSTEM IS BEING SHOWN AT THIS
 TIME, REVIEW OF SUCH SYSTEM FOR CODE
 COMPLIANCE CAN NOT BE DONE.
  
 5) NOTE: PLEASE SEE COMPLETE VALUATION
 FOR COMPLETE SCOPE OF WORK AS INDICATED
 ON PLANS SAHLL INCLUDE ALL LABOUR AND
 MATERIALS WHETHER OR NOT AN EUIPMENT/
 MATERIALS ARE OWNER SUPPLIED. FBC 108.3
 PLEASE SEE APPLIED VALUE SEEMS LOW FOR
 SCOPE SHOWN AND NEW EQUIPMENT BEING
 INDICATED. PLEASE KNOW, IF THE VALUE IS
 NOT ADJUSTED, ONE WILL BE ADJUSTED PER
 'MARSHALL'S & SWIFT" GUIDES AS ADOPTED
 ON THE FBC.
  
 6) NOTE: PLEASE INCLUDE AND SUBMIT
 MANUFACTURES SPECS/CUT SHEETS FOR ALL
 THE NEW UPS/ LEIBERT SYSTEM EQUIPMENT.
 PLEASE BE SURE THE SPECS INDICATE A
 LISTING FROM A NRTL.
  
 7) NOTE: PLEASE SEE NFPA-75, AND
 NFPA-70, 645 AS THE MDF ROOM SEEMS TO
 CLEARLY INDICATE AN "IT" ROOM. PLEASE
 SEE MECHANICAL REQUIREMENTS FOR RATED
 DMAPERS, SD'S.
 PLEASE SEE AN EPO IS BEING SHOWN,
 HOWEVER HOW THIS IS BEIGN TIED IN AND
 SHUNTING THE POWER COMING FROM "L2A1,
 L2A2 AND URL" IS UNCLEAR AT THIS TIME.
 PLEASE SEE NO MENTION IN THESE PANELS
 COULD BE LCOATED FOR SHUNT AND
 DISCONNECTING MEANS.
 645.1-.16
  
 8) NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AS ACCESS CONTROL SYSTEM(S) NEEDS TO BE
 VERIFIED. PLEASE SEE NFPA-101 AS A FAIL
 SAFE MODE/ BACK-UP IS REQUIRED SO THAT
 MEANS OF EGRESS MAY NOT BE IMPEDED.
 7.2.1.5
 PLEASE SEE THAT SYSTEM AS SHOWN IS NOT
 CLEAR OF CODE COMPLIANCE AT THIS TIME.
 PLEASE SEE THAT ANY COMMENTS FORM FIRE
 REVIEW WILL BE REQUIRED TO BE ADJUSTED
 ON ELECTRICAL PLANS.
  
 9) NOTE: PLEASE COMPLETE PANEL SCHEDULES
 INDICATING ALL CONDUCTOR SIZES AND
 CORRELATING WIHT THE OCP AS SHOWN.
 PLEASE SEE 240.4,310.16,408.4.
 THIS IS REQUIRED AT THIS TIME.
 FBC 106.1.2
  
 10) NOTE: PLEASE SUBMIT COMPLETED LOAD
 CALCULATIONS PER 220.3,220.10,220.11,
 210.13, ETC AND PLEASE SHOW ALL
 CONTINUOUS LOADS AT 125% 215.3,230.42
 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  