| Date |
Text |
| 2006-09-13 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE ARCHITECT'S TITLE BLOCK IS |
| | MISSING INFORMATION. SEE FAC 61G-15 FOR |
| | REQUIRED INFORMATION. |
| | |
| | 3) THE CODE ANALYSIS INFORMATION ON |
| | A0.00 LISTS INCORRECT CODE SECTION AND |
| | TABLE REFERENCES. PLEASE UPDATE TO 2004 |
| | EDITION OF THE FLORIDA BUILDING CODE. |
| | SEE NOTATIONS ON PLAN. |
| | |
| | 4) PLEASE SPECIFY THE NUMBER OF STORIES |
| | AND BUILDING HEIGHT. PLEASE CORRECT THE |
| | CONSTRUCTION TYPE LISTED ON SHEET A0.00. |
| | SPECIFY THE CONSTRUCTION TYPE USING THE |
| | 2004 FBC DESIGNATIONS. IF THIS IS A HIGH |
| | RISE STRUCTURE WITH OCCUPIED FLOORS MORE |
| | THAN 75 FEET ABOVE FIRE DEPARTMENT |
| | ACCESS (403.1), THE CONSTRUCTION TYPE |
| | PER TABLE 503 IS TYPE I-A OR I-B |
| | (DEPENDING ON THE BUILDING HEIGHT). |
| | |
| | 5) SPECIFY THE LEVEL OF ALTERATION FOR |
| | THE PROJECT. SEE THE 2004 EXISTING |
| | BUILDING CODE. |
| | |
| | 6) PLEASE CHANGE THE CODE REFERENCE IN |
| | DETAIL 4 ON A7.01 FROM IBC TO FBC. |
| | |
| | 7) DETAIL 10 ON SHEET A7.21 IS |
| | INCORRECTLY LABELED. IT SHOULD BE |
| | LABELED DETAIL 7. |
| | |
| | 8) PROVIDE ADDITIONAL STRUCTURAL DETAILS |
| | FOR THE ATTACHMENT OF THE MDF PANELS IN |
| | THE RECEPTION AREA CEILING. SPECIFY THE |
| | SPACING OF THE THREADED RODS, UNISTRUTS, |
| | BLOCKING Z-CLIPS, ETC. SPECIFY THE |
| | ATTACHMENT OF THE BLOCKING TO THE |
| | STRUTS. SPECIFY THE EMBED DEPTH OF THE |
| | ANCHORS FOR THE THREADED RODS. DETERMINE |
| | THAT THE SLAB THAT WILL BE DRILLED INTO |
| | IS NOT A TENSION SLAB. |
| | |
| | 9) SPECIFY THE SUITE NUMBER FOR THE |
| | PROJECT ON THE PERMIT APPLICATION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |