| 2006-09-07 00:00:00 | | | | | | | DENIED | | | | | | 1) FOOTINGS THAT SUPPORT WALLS SHALL BE | | | A MINIMUM OF 8" THICK, 12" IN WIDTH AND | | | A MINIMUM OF 12" BELOW GRADE PER 1805.2, | | | 1805.4.1 AND 1805.4.2.3 OF THE FLORIDA | | | BUILDING CODE | | | | | | 2) WHERE CONCRETE IS CAST AGAINST EARTH | | | THE MIN COVER FOR REBAR IS 3" PER TABLE | | | 1907.7.1 FBC | | | | | | 3) PLEASE STATE THE REBAR SIZES AND THE | | | CENTER TO CENTER SPACING OF THE VERTICAL | | | BARS | | | | | | 4) PLEASE BE AWARE THAT ALL FOOTINGS AND | | | WALLS MUST REMAIN ENTIRELY WITHIN THE | | | PROPERTY LINES THEREFORE THE FOOTINGS | | | SHALL BE AN OFFSET DESIGN | | | | | | 5) WALLS THAT RETAIN EARTH SHALL BE | | | DESIGNED TO RESIST THE UNBALANCED SOIL | | | LOADS THAT ARE IMPOSED AND ENSURE | | | STABILITY AGAINST OVERTURN, SLIDING,ETC. | | | PER 1806.2 FBC | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | |
|