Plan Review Notes
Plan Review Notes For Permit 06081441
Permit Number 06081441
Review Stop M
Sequence Number 1
Notes
Date Text
2006-08-18 00:00:00PROVISO:
 1.PLAN SHEET M1.1 & M1.2, TERMINATION
 OF THE EXHAUST SHALL COMPLY WITH 2004
 FMC 506.5.5 THE EXCEPTION REQUIRES 2FT
 HORIZONTAL DISTANCE BETWEEN THE PARAPET
 STRUCTURE AND THE DISCHARGE OF THE
 EXHAUST.PLEASE NOTE, THIS IS ONLY
 PERMITTED IF THE DISCHARGE IS HIGHER
 THAN THE TOP OF THE PARAPET.
  
 2.THE AIR VELOCITY WITHIN THE GREASE
 DUCT SYSTEM SHALL BE NOT LESS THAN 1,500
 FPM PERMIT AND NOT GREATER THAN 2,500
 FPM.
  
 3.PLEASE PROVIDE INSTALLATION
 INSTRUCTIONS FOR THE FIREWRAP ON THE
 JOBSITE FOR INSPECTION.PLEASE NOTE,
 WELDS ARE TO BE INSPECTED PRIOR TO
 COVERING.
  
 ADDITIONAL PERMIT & PLANS REQUIRED FOR
 FIRE SUPPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.