| Notes |
| Date |
Text |
| 2006-08-18 00:00:00 | PROVISO: | | | 1.PLAN SHEET M1.1 & M1.2, TERMINATION | | | OF THE EXHAUST SHALL COMPLY WITH 2004 | | | FMC 506.5.5 THE EXCEPTION REQUIRES 2FT | | | HORIZONTAL DISTANCE BETWEEN THE PARAPET | | | STRUCTURE AND THE DISCHARGE OF THE | | | EXHAUST.PLEASE NOTE, THIS IS ONLY | | | PERMITTED IF THE DISCHARGE IS HIGHER | | | THAN THE TOP OF THE PARAPET. | | | | | | 2.THE AIR VELOCITY WITHIN THE GREASE | | | DUCT SYSTEM SHALL BE NOT LESS THAN 1,500 | | | FPM PERMIT AND NOT GREATER THAN 2,500 | | | FPM. | | | | | | 3.PLEASE PROVIDE INSTALLATION | | | INSTRUCTIONS FOR THE FIREWRAP ON THE | | | JOBSITE FOR INSPECTION.PLEASE NOTE, | | | WELDS ARE TO BE INSPECTED PRIOR TO | | | COVERING. | | | | | | ADDITIONAL PERMIT & PLANS REQUIRED FOR | | | FIRE SUPPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|