Plan Review Notes
Plan Review Notes For Permit 06081415
Permit Number 06081415
Review Stop B
Sequence Number 2
Notes
Date Text
2006-08-24 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- FLAT ROOF SYSTEM WITH INSULATION
 PRODUCT APPROVAL SUBMITTED (NOA NO
 03-0501.09):
 A) CLEARLY IDENTIFY APPROVED ASSEMBLY
 TO BE INSTALLED AS REQUIRED BY CITY
 POLICY FOR RE-ROOFING PERMITS. SEE
 ATTACHED COPY.
  
 B) IF SELECTED APPROVED ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #7, THEN,
 PROVIDE COMPLETE RAS 117 CALCULATIONS.
 CALCULATIONS SHALL BE DONE AND SIGNED
 AND SEALED BY ANY ONE OF THE
 PROFESSIONALS LISTED IN THE GENERAL
 LIMITATION #7.
  
 C) IF SELECTED APPROVED ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #9, THEN
 THIS ASSEMBLY CAN'T BE USED IN THIS
 LOCATION. IT DOESN'T MEET THE DESIGN
 PRESSURES FOR THIS LOCATION. SEE TABLE
 1609.6B FBC 2004.
  
 2- PRODUCT APPROVAL NOA NO 06-0417.06 IS
 A COAT ROOF MAINTENANCE SYSTEM. IT NEEDS
 TO BE INSTALLED ON ANY OF THE SUBSTRATES
 IDENTIFYIED IN THE PRODUCT APPROVAL.
 CLARIFY IF THIS SYSTEM IS GOING TO BE
 INSTALLED OVER THE NEW FLAT ROOF
 SYSTEM?. SEE NOA FOR APPROVED SUBSTRATES
 TO VERIFY COMPLIANCE WITH THIS PRODUCT
 APPROVAL.
  
 3- NOTICE OF COMMENCEMENT DOESN'T
 PROVIDE THE GENERAL DESCRIPTION OF THE
 IMPROVEMENTS. PROVIDE SUCH INFORMATION
 AND RE-RECORD NOTICE OF COMMENCEMENT.
  
 4- NEW PERMIT APPLICATION SUBMITTED HAS
 THE SIGNATURE OF THE OWNER AND THE
 CONTRACTOR ON THE WRONG PLACE. REVISE AS
 REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712