2006-08-17 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- FLAT ROOF TILE (NOA # 06-0201.01)
 CAN'T BE INSTALLED IN FLAT ROOFS. SEE
 PRODUCT APPROVAL FOR MINIMUM ROOF SLOPE.
  
 2- CLEARLY SPECIFY WHICH FLAT ROOF
 SYSTEM IS GOING TO BE INSTALLED AND
 PROVIDE ALL INFORMATION AS REQUIRED BY
 CITY POLICY FOR RE-ROOFING PERMITS.SEE
 ATTACHED COPY OF CITY POLICY AND PROVIDE
 ALL THE INFORMATION..
  
 3- THERE ARE 2 DIFFERENT PRODUCT
 APPROVALS SUBMITTED FOR FLAT ROOF.
 PROVIDE COMPLETE INFORMATION ONLY FOR
 PRODUCT TO BE INSTALLED.
  
 4- FLAT ROOF REQUIRES NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS. SEE TABLE
 1609.6B FBC 2004. PROVIDE ALL
 INFORMATION AS REQUIRED BY GENERAL
 LIMITATION #7.
  
 ***NOTE: IF FLAT ROOF ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #9, THEN
 IT CAN'T BE USED BECAUSE ADDITIONAL NAIL
 ENHANCING IS NOT ALLOWED.
  
 5- PROVIDE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7.
 CALCULATIONS TO BE PERFORMED BY PEOPLE
 LISTED IN GENERAL LIMITATION #7. SEE
 GENERAL LIMITATIONS ON LAST PAGE OF DADE
 COUNTY NOA SUBMITTED.
  
 6- REVISE PERMIT APPLICATION AND NOTICE
 OF COMMENCEMENT. CORRECT FBC CHAPTER FOR
 ROOFS IS CHAPTER 15 FBC 2004, NOT
 CHAPTER 9. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712