| 2006-08-17 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- FLAT ROOF TILE (NOA # 06-0201.01) |
| | CAN'T BE INSTALLED IN FLAT ROOFS. SEE |
| | PRODUCT APPROVAL FOR MINIMUM ROOF SLOPE. |
| | |
| | 2- CLEARLY SPECIFY WHICH FLAT ROOF |
| | SYSTEM IS GOING TO BE INSTALLED AND |
| | PROVIDE ALL INFORMATION AS REQUIRED BY |
| | CITY POLICY FOR RE-ROOFING PERMITS.SEE |
| | ATTACHED COPY OF CITY POLICY AND PROVIDE |
| | ALL THE INFORMATION.. |
| | |
| | 3- THERE ARE 2 DIFFERENT PRODUCT |
| | APPROVALS SUBMITTED FOR FLAT ROOF. |
| | PROVIDE COMPLETE INFORMATION ONLY FOR |
| | PRODUCT TO BE INSTALLED. |
| | |
| | 4- FLAT ROOF REQUIRES NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS. SEE TABLE |
| | 1609.6B FBC 2004. PROVIDE ALL |
| | INFORMATION AS REQUIRED BY GENERAL |
| | LIMITATION #7. |
| | |
| | ***NOTE: IF FLAT ROOF ASSEMBLY IS |
| | LIMITED BY GENERAL LIMITATION #9, THEN |
| | IT CAN'T BE USED BECAUSE ADDITIONAL NAIL |
| | ENHANCING IS NOT ALLOWED. |
| | |
| | 5- PROVIDE RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7. |
| | CALCULATIONS TO BE PERFORMED BY PEOPLE |
| | LISTED IN GENERAL LIMITATION #7. SEE |
| | GENERAL LIMITATIONS ON LAST PAGE OF DADE |
| | COUNTY NOA SUBMITTED. |
| | |
| | 6- REVISE PERMIT APPLICATION AND NOTICE |
| | OF COMMENCEMENT. CORRECT FBC CHAPTER FOR |
| | ROOFS IS CHAPTER 15 FBC 2004, NOT |
| | CHAPTER 9. REVISE AS REQUIRED. |
| | |