| 2006-10-20 07:58:38 | | | | | | | DENIED | | | | | | 1) PLEASE NOTE THE CORRECTION MADE TO PLAN AS PREVIOUS | | | COMMENT REGUARDING SHUTTER SPAN WAS NOT CORRECTED, | | | PANEL CANNOT BE MOUNTED HORIZONTALLY BECAUSE IT WOULD | | | EXCEED THE MAXIMUM ALLOWABLE SPAN FOR THE PRESSURE | | | SHOWN (MAX SPAN 85") OPENING IS 93" + 6" EDGE DISTANCE | | | = 99" THEREFORE PANEL SHALL BE INSTALLED VERTICALLY | | | | | | 2) ALSO THE SHUTTER SPANSON THE SCHEDULE INDICATE | | | THAT THE PANELS ARE MOUNTED HORIZONTALLY AS THEY ARE 2" | | | LARGER THAN THE WIDTH PLEASE VERIFY THIS | | | | | | 3) PRODUCT APPROVALS SHOW AN EDGE DISTANCE OF 31/2" | | | THEREFORE THE PANEL LENGTH/SPANS SHOULD BE APPROX 7" | | | LARGER THAN THE OPENING SIZE (HORZ FOR WIDTH VERT FOR | | | HEIGHT) | | | | | | 4) PER 713.13(2) F.S. | | | IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT | | | COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS | | | VOID | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | |
|