| Plan Review Notes For Permit 06081269 |
| Permit Number |
06081269 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-24 00:00:00 | | | | | | | DENIED | | | | | | 1) PRODUCT APPROVALS FOR MODIFIED SHALL | | | CONTAIN THE APPROVED MATERIAL PAGES 2-9 | | | OF PRODUCT APPROVAL | | | | | | 2) IF THIS IS A RECOVER IT SHALL FIRST | | | BE PRE-INSPECTED PLEASE CONTACT KEN | | | CONRAD AT 805-6666 | | | | | | 3) THE SYSTEM THAT WAS CHOSEN HAS A | | | DESIGN PRESSURE OF -45 PSF (IN OUR | | | JURISTICTION THE WIND LOADS OF 140 MPH | | | EXP B REQUIRE THAT THE EDGE ZONES MEET | | | OR EXCEED -59.2 AND THE CORNER ZONES | | | MEET OR EXCEED -89.0) THE SYSTEM CHOSEN | | | IS ALSO A LIMITATION 9 WHICH CANNOT BE | | | ENHANCED | | | | | | 4) WHEN MIXED ROOFING IS USED SUCH AS | | | ROOF TILE AND BUR SPECIFY HOW MANY | | | SQUARES OF EACH TYPE OF ROOF | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|