| Plan Review Notes For Permit 06081258 |
| Permit Number |
06081258 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-25 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE A CALCULATION INCLUDI- | | | NG ALL ADDED LOADS ,ALL EXISTING LOADS | | | AND THE EXISTING OR PROPOSED SERVICE | | | SPECIFICATIONS PER 215.15. | | | | | | 2} PLEASE PROVIDE A PANEL SCHEDULE SO | | | THAT BRANCH/FEEDER CIRCUIT CONDUCTOR AND | | | OVER CURRENT PROTECTION COMPLIANCE MAY | | | BE REVIEWED PER 215.5 AND 106.3.5.4 FBC | | | AS AMENDED. INCLUDE NEW LOADS. | | | | | | 3}THE PERSON TAKING RESPONSIBILITY FOR | | | THE DESIGN MUST PRINT AND SIGN THEIR | | | NAME TO SAME PER 106.3.4.2. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|