Date Text
2006-08-25 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A CALCULATION INCLUDI-
 NG ALL ADDED LOADS ,ALL EXISTING LOADS
 AND THE EXISTING OR PROPOSED SERVICE
 SPECIFICATIONS PER 215.15.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT BRANCH/FEEDER CIRCUIT CONDUCTOR AND
 OVER CURRENT PROTECTION COMPLIANCE MAY
 BE REVIEWED PER 215.5 AND 106.3.5.4 FBC
 AS AMENDED. INCLUDE NEW LOADS.
  
 3}THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  
  
  