Plan Review Notes
Plan Review Notes For Permit 06081216
Permit Number 06081216
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-09 08:33:02 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW. THIS IS THE SECOND REQUEST FOR THESE COMMENTS.
 THE CHANGES TO THE PLAN MUST BE DONE BY THE DESIGNER OF
 RECORD PER 471 FS.
  
 1} THE ELECTRICAL CONNECTION TO THE
 BOOTH IS NOT SHOWN. PLEASE SHOW THE
 LOCATION OF CONNECTIONS AND COMPLIANCE
 WITH 516 NEC AND NFPA-33, CHAPTER 6.
  
 2} PLEASE INDICATE PANEL LOCATION,
 DESIGNATION, AND BRANCH CIRCUIT NUMBERS
 FEEDING THE BOOTH.
  
 3} THE REFERENCE TO THE 2003 NEC IN THE
 NOTES IS INCORRECT AND SHOULD READ 2002,
 WHICH IS THE ONE ADOPTED BY STATUTE.
  
 4} THE REFERENCE TO SBCCI FL FIRE
 PREVENTION CODE, IS ALSO OUTDATED AND NO
 LONGER IN USE.
 PLEASE ELIMINATE ALL REFERENCES THAT DO
 NOT APPLY, AND USE THE CORRECT CODE
 REFERENCED BY THE 2004 FBC, IN THE
 NOTES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718