| Plan Review Notes For Permit 06081216 |
| Permit Number |
06081216 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-01-09 08:33:02 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. THIS IS THE SECOND REQUEST FOR THESE COMMENTS. | | | THE CHANGES TO THE PLAN MUST BE DONE BY THE DESIGNER OF | | | RECORD PER 471 FS. | | | | | | 1} THE ELECTRICAL CONNECTION TO THE | | | BOOTH IS NOT SHOWN. PLEASE SHOW THE | | | LOCATION OF CONNECTIONS AND COMPLIANCE | | | WITH 516 NEC AND NFPA-33, CHAPTER 6. | | | | | | 2} PLEASE INDICATE PANEL LOCATION, | | | DESIGNATION, AND BRANCH CIRCUIT NUMBERS | | | FEEDING THE BOOTH. | | | | | | 3} THE REFERENCE TO THE 2003 NEC IN THE | | | NOTES IS INCORRECT AND SHOULD READ 2002, | | | WHICH IS THE ONE ADOPTED BY STATUTE. | | | | | | 4} THE REFERENCE TO SBCCI FL FIRE | | | PREVENTION CODE, IS ALSO OUTDATED AND NO | | | LONGER IN USE. | | | PLEASE ELIMINATE ALL REFERENCES THAT DO | | | NOT APPLY, AND USE THE CORRECT CODE | | | REFERENCED BY THE 2004 FBC, IN THE | | | NOTES. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|