| Plan Review Notes For Permit 06081216 |
| Permit Number |
06081216 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-08 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE PROVIDE NOTE TO PLANS | | | INDICATING HOW THE PREVENTION OF STATIC | | | ELECTRICITY WILL OCCUR. | | | | | | 2) OCCUPANT NOTIFICATION APPLIANCE IS | | | REQUIRED. IF BUILDING IS PROTECTED BY | | | FIRE ALARM SYSTEM, THE SPRAY BOOTH SHALL | | | BE CONNECTED TO THE FIRE ALARM SYSTEM. | | | | | | 3) PLEASE PROVIDE INFORMATION REGARDING | | | WHAT TYPE OF FIRE PROTECTION SYSTEM TO | | | BE USED, SPRINKLER OR DRY CHEMICAL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|