| 2006-08-21 00:00:00 | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 2} THE PERSON TAKING RESPONSIBILITY FOR |
| | THE DESIGN MUST PRINT AND SIGN THEIR |
| | NAME TO SAME PER 106.3.4.2. |
| | |
| | THIS APPLICATION WAS GIVEN TO THE |
| | CHIEF ELECTRICAL INSPECTOR TO DETERMINE |
| | COMPLIANCE WITH ARTICLE 230.2 2002 NEC. |
| | |
| | THE CHIEF ELECTRICAL INSPECTOR WILL NOT |
| | GRANT PERMISSION TO ADD AN ADDITIONAL |
| | SERVICE TO THIS BUILDING WITHOUT THE |
| | APPLICANT SHOWING CAUSE UNDER 230.2(A) |
| | THROUGH (D). A COMPLETE LOAD CALCULATION |
| | FOR THE EXISTING SERVICE, INCLUDING |
| | CALCULATIONS ON ALL SEPARATE BUSINESSES, |
| | ON THE SERVICE NOW SUPPLYING THE UNIT. |
| | |
| | A VOLTAGE DROP CALCULATION IS ALSO |
| | REQUIRED TO BE SUBMITTED, FROM FPL VAULT |
| | TO THE FIRST OVERCURRENT DEVICE ON THE |
| | LOAD SIDE OF THE METER IF GRANTED |
| | PERMISSION TO INSTALL. |
| | |