| Plan Review Notes For Permit 06080957 |
| Permit Number |
06080957 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-25 00:00:00 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1}PLEASE SUBMIT DETAILS FOR THE PANEL | | | SHOWN ON THE SCHEMATIC. FEEDER AND CONDU | | | IT SIZE AND TYPE, PANEL RATING AND OCP, | | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | | THE PANEL ON THE SCHEMATIC APPEARS TO | | | BE A POOL PANEL. IF EXISTING VERIFY SAME | | | AND DISREGARD THE PREVIOUS COMMENT. IF | | | BEING INSTALLED AS PART OF THIS PROJECT | | | THE ABOVE INFORMATION IS NEEDED. BE SURE | | | THE ENGINEER SEES THIS COMMENT AND | | | ADDRESSES SAME ON ALL FUTURE POOLS | | | SUBMITTED TO AVOID DELAYS IN PERMITTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|