Plan Review Notes
Plan Review Notes For Permit 06080911
Permit Number 06080911
Review Stop P
Sequence Number 1
Notes
Date Text
2006-08-18 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING AND GAS PLAN REVIEW. PLEASE
 REFERENCE CORRECTED DRAWING IN RED INK
 FOR RESUBMITTAL :
  
 1. PER CHAPTER 1, SECTION 106, PLEASE
 SUBMIT A DRAWING INDICATING EXISTING
 FLOOR PLAN LAY-OUT OF WASHING MACHINE
 AND A SEPERATE DRAWING INDICATING THE
 NEW PROPOSED WASHING MACHINE LAY-OUT.
 2. PER FBC-2004 PLUMBING THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE WASHING
 MACHINE.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. ( NOTE: THE DRAINAGE STACK IS
 SIZED WRONG.)
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE STANDPIPE
 ON THE CORRECTED DRAWING.
 3. PER FBC-2004 PLUMBING THE FOLLOWING
 INFORMATION ON CLEANOUTS NEEDS TO BE
 INDICATED ON THE CORRECTED DRAWING FOR
 RESUBMITTAL.
 (A) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (B) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. CLEANOUTS FOR
 WASHING MACHINES SHALL BE LOCATED 4'
 ABOVE FINNISH FLOOR (AFF). PLEASE NOTE
 THIS ON DRAWING.
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
  
 NOTE: A SEPERATE PERMIT IS REQUIRED FOR
 THE GAS SYSTEM WITH THE FOLLOWING
 INFORMATION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. NOTE: THE DRAWING
 SUBMITTED FOR THE GAS PIPE IS NOT AN
 ISOMETRIC.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 10. FBC-2004 CHAPTER 1,SECTION
 106.3.4.2: THE PERSON RESPONSIBLE FOR
 THE DESIGN OF THE DRAWING SHALL CLEARLY
 PRINT AND SIGN NAME, AND ALSO DATE
 DRAWING. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  