| 2007-02-07 16:00:46 | | | | ****************PROVISO**************** | | | A} PER FBC-2004 FUEL GAS SECTION 404.4: ALL METALLIC | | | PIPING TO BE ABOVE GROUND AND PROTECTED AGAINST | | | CORROSION BY PAINTING PIPE. | | | B} PER FBC-2004 FUEL GAS SECTION 407.2: PIPING SHALL | | | BE PROVIDED WITH SUPPORT BY STRAPPING TO WALL. | | | C} PER FBC-2004 FUEL GAS SECTION 408.4: SEDIMENT TRAP | | | REQUIRED FOR TANKLESS WATER HEATER. | | | D} PER INDICATED TABLE 402.4(2) GAS SYSTEM IS NATURAL | | | GAS. |
|