| Plan Review Notes For Permit 06080902 |
| Permit Number |
06080902 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-24 00:00:00 | BUILDING DENIED | | | | | | 1) FAC 61G1-16 REQUIRES THE FIRM'S | | | LICENSE NUMBER IN THE TITLE BLOCK. | | | | | | 2) SPECIFY THE TYPE OF CONSTRUCTION PER | | | FBC 602. | | | | | | 3) SPECIFY THE LEVEL OF ALTERATION PER | | | 2004 EXISTING BUILDING CODE 301.5. | | | | | | 4) IF THIS IS A TYPE I OR II | | | CONSTRUCTION COMBUSTIBLE MATERIALS MUST | | | COMPLY WITH FBC 603.1. PLEASE REVISE THE | | | NOTES FOR WOOD AND PLASTICS ON SHEET A4. | | | | | | 5) SPECIFY THE LOCATIONS OF THE EXITS | | | REQUIRED FOR THE OFFICE THAT WILL BE | | | REVISED TO OPEN INTO THE ADJACENT TENANT | | | SPACE. | | | | | | 6) THE DOOR HARDWARE SHALL COMPLY WITH | | | FBC 11-4.13.9. | | | | | | 7) FIRE SPRINKLER PLANS WILL BE REQUIRED | | | FOR ANY HEADS THAT REQUIRE RLOCATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|