| Plan Review Notes For Permit 06080864 |
| Permit Number |
06080864 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-23 00:00:00 | | | | | | | DENIED | | | | | | 1) PLEASE HAVE THE ENGINEER OF RECORD | | | PROVIDE 2 COPIES OF A SIGNED AND SEALED | | | LETTER THAT THE PRODUCT WILL BE ASSESSED | | | AFTER IT IS INSTALLED FOR QUALITY | | | ASSURANCE.ALSO ADD ENGINEER TO ITEM 8 | | | LIST FOR QUALITY ASSURANCE ENTITY ON | | | PAGE 2 OF THE SITE SPECIFIC APPLICATION | | | | | | 2) PROVIDE ENGINEERED SUBSTRATE | | | ATTACHMENT FOR WOOD BUCKS PER 1714.5.4.1 | | | FBC | | | | | | 3) PRODUCT APPROVAL FOR STORM PANELS HAS | | | BEEN REVISED PLEASE SUBMIT NEW APPROVALS | | | ALSO BE SURE TO MARK DRAWINGS WITH | | | ATTACHMENT METHOD, ANCHOR TYPE, ETC THAT | | | WILL BE USED | | | | | | 4) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|