2007-05-03 16:02:34REVISION: CHANGE LAYOUT AND LENGTH OF PIPE.
  
 ****************PROVISO****************
 A}PER FBC-2004 FUEL GAS SECTION 409.5 EQUIPMENT
 SHUTOFF VALVE: EACH APPLIANCE SHALL BE PROVIDED WITH A
 SHUTOFF VALVE SEPERATE FROM THE APPLIANCE. THE SHUTOFF
 VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE
 APPLIANCE, NOT FURTHER THAN 6 FEET FROM THE APPLIANCE,
 AND SHALL BE INSTALLED UPSTREAM FROM THE UNION,
 CONNECTOR OR QUICK DISCONNECT DEVICE IT SERVES. SUCH
 SHUTOFF VALVES SHALL BE PROVIDED WITH ACCESS.
  
 B} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 C} PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT TRAP
 SHALL BE INSTALLED DOWNSTREAM OF THE EQUIPMENT SHUTOFF
 VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS
 PRACTICAL.