Plan Review Notes
Plan Review Notes For Permit 06080861
Permit Number 06080861
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-01 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1) PROVIDE A PANEL SCHEDULE FOR THE
 EMERGENCY/GENERATOR PANEL(S). CALCULATE
 THE LOADS FOR THE INDIVIDUAL PANELS AS
 IT APPEARS TWO PANELS ARE BEING FED FROM
 THE ATS. PLEASE CLARIFY.
  
 2} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW