| Plan Review Notes For Permit 06080861 |
| Permit Number |
06080861 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-01 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1) PROVIDE A PANEL SCHEDULE FOR THE | | | EMERGENCY/GENERATOR PANEL(S). CALCULATE | | | THE LOADS FOR THE INDIVIDUAL PANELS AS | | | IT APPEARS TWO PANELS ARE BEING FED FROM | | | THE ATS. PLEASE CLARIFY. | | | | | | 2} THERE MUST BE A DISCONNECT FROM THE | | | GENERATOR WHERE THE CONDUCTORS ENTER THE | | | BUILDING. IF ALL DISCONNECTS CANNOT BE | | | GROUPED PER 230.72, SEE THAT ALL | | | ARTICLES FROM 225.31 THROUGH 225.39, ARE | | | COMPLIED WITH. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|