| Plan Review Notes For Permit 06080678 |
| Permit Number |
06080678 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-23 18:38:19 | **** UNSAT **** | | | AS REVISIONS WERE SUBMITTED UDNER THE WRONG PERMIT | | | NUMBER, PLANS FROM FRONT COUNTER SUPERVISOR ON | | | 10/23/06 | | | | | | | | | 1) NOTE: PLEASE SEE A PREMIT WAS ISSUED TO REMOVE AND | | | REPLACE ELECTRICAL RECEPTS/DEVICES ONLY. PLEASE KNOW AS | | | SHOWN THE SCOPE HAS COMPLETELY CHANGED. | | | PLEASE PROVIDE INFORMATION ON PLANS FOR COMPLIANCE WITH | | | 225.31-225.39. | | | PLEASE PROVIDE GROUNDING PER 250.32 | | | PLEASE SEE MISSING DEDICATED BATH CIRCUIT PER | | | 250.52D,210.11C3 | | | PLEASE SEE ALL DEDICATE DAND CIRCUITS SHALL BE SHOWN ON | | | PANEL SCHEDULE. 240.4,310.16, ETC. | | | | | | FBC 106.1.2, 106.3.5.4 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 |
|