| Date |
Text |
| 2006-12-20 16:13:33 | *** DENIED *** |
| | 1) AS REQUESTED IN LAST REVIEW, ENTER ALL REQUIRED |
| | INFORMATION ON ENERGY CALCULATIONS, SEE HIGH LIGHTS ON |
| | ENERGY CAL'S. |
| | |
| | 2) EQUIPMENT LISTING ON MECHANICAL PLANS IS DIFFICULT |
| | TO READ. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY. PER 2004 FBC 106.1.1. |
| | |
| | 3) PLEASE SHOW ON THE MECHANICAL PLANS THE SIZE OF THE |
| | RETURN AIR GRILL TO THE AIR HANDLER. |
| | |
| | 4) PLEASE PROVIDE FOR RETURN AIR TO BEDROOMS.BALANCED |
| | RETURN AIR MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | . |