| 2007-01-08 17:28:33 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- ARCHITECT NEEDS TO PROVIDE ALL REQUIRED INFORMATION |
| | IN THE TITLE BLOCK AS REQUIRED BYFLORIDA |
| | ADMINISTRATIVE CODE SEC. 61G1-16.004. |
| | |
| | 2- IMPACT FEES STAMP STATES ADDITION TO BE 166SF, WHILE |
| | SHEET 2 OF 6 CALLS FOR NEW LIVING AREA TO BE 1528SF. |
| | BRING DRAWINGS TO PALM BEACH COUNTY TO REVISE IMPACT |
| | FEES STAMP WITH CORRECT ADDITIONAL SQUARE FOOTAGE. |
| | BRING BACK RE-STAMPED DRAWINGS AND COPY OF PAID RECEIPT |
| | IF ADDITIONAL FEES ARE DUE. |
| | |
| | 3- SPECIFY ATTIC ACCESS SIZE AS REQUIRED BY SEC. R807 |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 4- LEVEL OF ALTERATION NEEDS TO BE IDENTIFIED AS |
| | REQUIRED BY SEC. 301.5 OF 2004 FLORIDA EXISTING CODE. |
| | |
| | 5- ARCHITECT TO SPECIFY ALL DESIGN CRITERIA AS REQUIRED |
| | BY SEC. R301 2004 FLORIDA RESIDENTIAL CODE. INCLUDE ALL |
| | DEAD LOADS, LIVE LOADS, ETC. |
| | ALSO, SHEET 3 OF 6 DOESN'T IDENTIFY THE BUILDING CODE |
| | AND SPECIFIC EDITION. IT'S ALSO MISSING THE DESIGN |
| | PRESSURES FOR WINDOW OPENINGS. ONLY DOORS DESIGN |
| | PRESSURES WERE GIVEN. |
| | |
| | 6- PROVIDE TRUSS DRAWINGS COMPLETE PACKAGE REVIEWED AND |
| | APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION AS |
| | REQUIRED BY SEC. R802.10.1 2004 FLORIDA RESIDENTIAL |
| | CODE. SEE THIS SECTION TO MAKE SURE ALL REQUIRED |
| | INFORMATION IS SUBMITTED. THIS INFORMATION NO NEED TO |
| | BE SUBMITTED RIGHT AWAY, BUT BEFORE INSTALLATION TO |
| | AVOID DELAYS OR CONFLICTS. |
| | |
| | 7- A) PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS. |
| | PROVIDE KEY PLAN AND COMPLETE INSTALLATION SCHEDULE |
| | (SEE ATTACHED SAMPLE) OR ANY WAY THAT WILL PROVIDE ALL |
| | REQUIRED INFORMATION FOR PLAN REVIEW AS SHOWN ON |
| | INSTALLATION SCHEDULE.SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | B) PRODUCT APPROVAL TO BE REVIEWED AND APPROVED IN |
| | WRITING (NOT SIGNING AND SEALING) AS REQUIRED BY SEC. |
| | 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- ENERGY CALCULATIONS: |
| | A) PROVIDE SPECIFICATIONS/CALCULATIONS SHOWINGOF |
| | HOW R2.5 INSULATION IS ACHIEVED ON CONCRETE SLAB. |
| | |
| | B) CEILING FANS CREDIT IS TAKEN. THEREFORE, SPECIFY |
| | SIZE OF CEILING FANS ON ALL ROOMS AS REQUIRED BY TABLE |
| | 13-607.1.A.1 2004 FBC. ALL CEILINGS FANS MUST BE |
| | INSTALLED FOR INSPECTION. |
| | |
| | C) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| | |
| | 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) PRECAST LINTELS. NEED CURRENT NOA FOR 8" LINTELS. |
| | ONE SUBMITTED IS FOR 4", 6" AND 12" LINTELS NOT FOR 8". |
| | SEE PLANS FOR LINTEL SIZE SPECIFIED. |
| | |
| | B) SLIDING GLASS DOORS. SEE PLANS FOR SIZE. |
| | |
| | C) ALL STRUCTURAL CONNECTORS SPECIFIED ON TRUSS |
| | CONNECTOR SCHEDULE AND IN ALL DETAILS AND NOTES. SEE |
| | PLANS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND |
| | PAGE SHOWING EACH CONNECTOR ONLY. NO NEED TO SUBMIT THE |
| | WHOLE LONG REPORT. |
| | |
| | D) ENTRY DOOR. |
| | |
| | E) SINGLE HUNG WINDOWS. NOA 05-0112.01 SUBMITTED |
| | EXPIRED ON 10/08/06. NEED CURRENT ONE. |
| | |
| | F) GARAGE SIDE AND REAR DOOR. NOA 02-0805.03 |
| | SUBMITTED IS FOR DOUBLE DOORS ONLY. NEED PRODUCT |
| | APPROVAL FOR SINGLE DOORS AS SHOWN ON PLANS. |
| | |
| | G) 12' WIDE X 7' HIGH GARAGE DOOR. NOA 03-0430.04 |
| | SUBMITTED IS FOR 9' WIDE DOORS ONLY. |
| | |
| | 10- ARCHITECT TO REVIEW PRODUCT APPROVAL FOR GARAGE |
| | SIDE AND REAR DOOR. IF PRODUCT APPROVAL REQUIRES 2X |
| | STRUCTURAL BUCK, THEN PROVIDE SUCH DETAIL. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 12- SPECIFY GARAGE OPENING PROTECTION AS REQUIRED BY |
| | SEC. R309 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 13- SHEET 5 OF 6: |
| | A) SPECIFY UPLIFT LOADS AND CONNECTORS AT THE ENDS |
| | OF GIRDER TRUSS ABOVE INTERIOR BEARING WALL.AND, |
| | SPECIFY STUDS TO RECEIVE GIRDER TRUSS BY BEDROOM #3. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | B) SPECIFY TRUSS CONNECTORS FOR TRUSSES RESTING ON |
| | EXISTING MASONRY WALL.HETA CONNECTORS NEED TO BE |
| | EMBEDED IN CONCRETE. NEED RETROFIT CONNECTOR. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | C) SEE CURRENT SIMPSON CATALOGUE AND REVISE ALL |
| | SPECIFIED CONNECTORS IF NUMBER AND TYPE OF FASTENERS |
| | DON'T MATCH THE ONES TESTED AND PUBLISHED BY THE |
| | MANUFACTURER'S. OTHERWISE, PROVIDE COMPLETE ENGINEERING |
| | ANALYSIS FOR FASTENERS THAT DIFFER FROM THOSE ALREADY |
| | PUBLISHED.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | SEE ALL CONNECTORS SPECIFIED THROUGHOUT THIS PAGE AND |
| | REVISE AS REQUIRED.CONNECTORS ARE TAKEN FROM SIMPSON |
| | 2004 CATALOGUE AND USP 2003 CATALOGUE. UPDATE AS |
| | REQUIRED. SEE COMMENTS ON PLANS. |
| | |
| | D) REVISE CONNECTOR B. IT CALLS FOR (2) HETA20 AT |
| | EACH END OF TRUSS. THIS CONNECTOR CAN'T BE INSTALLED ON |
| | WOOD TO WOOD CONNECTION. ALSO, IT CAN'T BE INSTALLED ON |
| | EXISTING WALL. REVISE AS REQUIRED. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 14- DRAWINGS SHOWREVISED SQUARE FOOTAGE AREAS. |
| | PERMIT VALUATION WAS UPDATED ACCORDINGLY. THEREFORE, |
| | OWES $542.74 FOR PERMIT VALUATION AND RADON FEES. |
| | |
| | 15- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS IF |
| | WORK IS NOT STARTED.SEC. 713.13 FLORIDA STATUTES. |
| | NEED RE-RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |