| Plan Review Notes For Permit 06080583 |
| Permit Number |
06080583 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-11-21 12:19:00 | MECHANICAL REVISION PAGE M-1 | | | *** PROVISO *** | | | 1) SEE HIGH LIGHTS ON MECHANICAL PLAN. | | | | | | 2) SEE HEAT DUCT TO OPEN OFFICE #414 MUST BE | | | CONSTRUCTED OF 0.0217" OF STEEL OR GREATER, SHELL NOT | | | BE EXCEED 100 SQUARE INCHES, AND MEET THE EXCEPTION | | | UNDER 2004 FBC/M 607.53, OR IT WILL REQUIRE A FIRE | | | DAMPER BE INSTALLED). | | | | | | 3) SEE EXISTING ELECT. ROOM #415 WALLS SHELL NOT BE | | | RATED, IF SO PROVIDE FIRE DAMPERS, PER 2004 FBC/M | | | 607.5.2 AND 607.5.3. | | | | | | 4) SEE 7" AND 10"DUCTS ENTERING OFFICE STORAGE ROOM | | | #406, MUST BE CONSTRUCTED OF 0.0217" OF STEEL OR | | | GREATER, AND MEET THE EXCEPTION UNDER 2004 FBC/M | | | 607.53, OR THEY WILL REQUIRE A FIRE DAMPER BE | | | INSTALLED. | | | | | | 5) SEE HEAT DUCT 12X6 TO OFFICE #407, MUST BE | | | CONSTRUCTED OF 0.0217" OF STEEL OR GREATER, AND MEET | | | THE EXCEPTION UNDER 2004 FBC/M 607.53, OR IT WILL | | | REQUIRE A FIRE DAMPER BE INSTALLED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|