| 2006-09-24 00:00:00 | ** UNSAT 2ND REVIEW ** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEEDOF |
| | ADDRESSING. |
| | NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: NO, ANY SYSTEM IS NOT SHOWN, |
| | PLEASE SEE LIGHTING PLANS REMAINED |
| | UNCHANGED. PLEASE INDICATE ALL DEVICES |
| | AND ,LOCATIONS.PLEASE SEE SEPARATE |
| | SPACES. |
| | PLEASE SEE NO LPD SUBMITTED, OR SHOWN ON |
| | PLANS. |
| | PLEASE INDICATE SYMBOLS ON PLANS AND |
| | CORRELATE WITH SYMBOL LIST FOR DEVICES. |
| | |
| | ** PEVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC 2004 CHAPTER 13. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR |
| | LIGHTING CONTROLS REQUIRED. |
| | PLEASE PROVIDE INFORMATION FOR DEVICES. |
| | IF OVER RIDES ARE TIMER (4HRSMAX) IF |
| | SENSOR TYPE (30MINS MAX) PLEASE |
| | INDICATE. |
| | PLEASE SEE LIGHTING POWER DENSITIES. |
| | 13-415.2.ABC.1, TABLES 415.2.C.1. |
| | 415.2.B.1 |
| | |
| | 3) NOTE: OK. |
| | |
| | ** NEW NOTE ** |
| | |
| | 4) NOTE: PLEASE SEE PLANS INDICATE AN |
| | "IT" ROOM, THIS WAS NOT NOTED ON |
| | PREVIOUS REVIEW. IF INDEED THIS IS A |
| | TRUE "IT" ROOMS, PLEASE INDICATE ALL |
| | REQUIREMENTS FOR SHUTTING DOWN |
| | POWER/EPO, CONSTRUCTION FOR |
| | ARCHITECTURAL FOR MIN 1HR TO ROOF DECL |
| | NFPA-75 2002. |
| | NEC 645, 2002 |
| | |
| | 5) NOTE: NOTICE GIVEN TO FS 553.80(2)(B) |
| | WITH RESPECT TO REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |