| Date |
Text |
| 2006-08-24 00:00:00 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE CLARIFY IF THE CONTINOUS |
| | LOADS ARE SHOWN AT 125%.215.3,230.42 ETC |
| | |
| | 2) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR |
| | LIGHTING CONTROLS REQUIRED. |
| | PLEASE PROVIDE INFORMATION FOR DEVICES. |
| | IF OVER RIDES ARE TIMER TYPE (4HRS MAX) |
| | IF SENSOR TYPE (30MINS MAX) PLEASE |
| | INDICATE. |
| | PLEASE SEE LIGHTING POWER DENSITIES. |
| | 13-415.2.ABC.1, TABLES 415.2.C.1. |
| | 415.2.B.1 |
| | |
| | |
| | 3) NOTE: PLEASE BE SURE THE FOLLOWING |
| | CODES AT STATED ON PLANS AT A MIN. |
| | 2002 NFPA-72, 2003 NFPA-101, 2004 FBC. |
| | 2002 NEC IS ALREADY ON PLANS. |
| | |
| | 4) NOTE: PLEASE VERIFY THE PANEL 5LL |
| | CONTAINING A MCB TO MEET 240.21 AND |
| | 408.16. PLEASE KNOW, IF ONE IS NOT |
| | EXISTING, ONE WILL BE REQUIRED TO BE |
| | INSTALLED. |
| | PLEASE VERIFY. |
| | |
| | 5) NOTE: PLEASE SEEPLANS IN ONE SET OF |
| | THE TWO ARE NOT SIGNED, DATED OR SEAL |
| | FOR BOTH ELECTRICAL SHEETS, ONE |
| | MECHANICAL AND THREE OF THE |
| | ARCHITECTURALS. |
| | PLEASE KNOW, SIGNING AND SEALING OF |
| | PLANS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL REVIEWER(S) WHETHER OR NOT COMMENT |
| | IS MADE BY THE OTHER REVIEWER(S). |
| | PLEASE SEE FS 481.221, 471.025 |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |