Plan Review Notes
Plan Review Notes For Permit 06080566
Permit Number 06080566
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-31 00:00:00 
  
  
  
  
  
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE COST OF LABOR AND MATERIAL
 FOR THE INSTALLATION OF ALL COMPONENTS
 UNDER THE SCOPE OF THIS PERMIT. FBC
 108.3.
  
 1} PROVIDE A RISER DIAGRAM SHOWING
 ELECTRICAL CONNECTION OF ALL SERVICE AND
 GENERATOR EQUIPMENT.
  
 2} THE SITE PLAN SUBMITTED DOES NOT
 CLARIFY THE PHYSICAL LOCATION OF THE
 EQUIPMENT. COMPLIANCE WITH ARTICLE 225
 CANNOT BE DETERMINED. PLEASE REDRAW AND
 LABEL IF SEPARATE LOCATIONS.
  
 3} THE LOAD CALCULATION EXCEEDS THE
 GENERATOR OUTPUT. SEE 702.5, CAPACITY
 AND RATING.
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE
 OPERATED AT ONE TIME. OPTIONAL STANDBY
 SYSTEM EQUIPMENT SHALL BE SUITABLE FOR
 THE MAXIMUM AVAILABLE FAULT CURRENT AT
 ITS TERMINALS. THE USER OF THE OPTIONAL
 STANDBY SYSTEM SHALL BE PERMITTED TO
 SELECT THE LOAD CONNECTED TO THE SYSTEM.
  
 4} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  
 5} PROVIDE MANUFACTURERS
 SPECIFICATIONS/RECOMMENDATION, REGARDING
 CLEARANCES.
  
 6} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 7} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  
  
  
  