Plan Review Notes
Plan Review Notes For Permit 06080559
Permit Number 06080559
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-10 00:00:00 
 NONCOMPLIANT
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
  
 2} INDICATE THE AMPERE RATING OF THE
 MAIN BREAKER IN THE NEW PANEL, VOLTAGE
 RATING, AND NUMBER OF CIRCUITS
 AVAILABLE.
  
 3} INDICATE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR PER 250.66, AND THE
 GROUNDING SYSTEM( WHAT IS BONDEED) PER
 250.52.
  
 4} INDICATE THE SERVICE CONDUCTOR SIZE,
 AND INDICATE OVERHEAD OR UNDERGROUND.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  