| Date |
Text |
| 2006-11-30 15:32:43 | ****** UNSAT2ND REVIEW ****** |
| | |
| | PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING, ALSO THERE ARE SOME NEW |
| | NOTES BASED ON SOME CHANGES ON PLANS. |
| | |
| | 1) NOTE: OK |
| | |
| | 2) NOTE: NO, PLEASE STILL CLARIFY SERVICE EQUIPMENT. IS |
| | THIS A 300A PANEL BOARD OF SOME KIND, A 300A METER MAIN |
| | COMBO WITH TWO MAINS? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE PLANS AND RISER. RISER SHOWS WHAT |
| | APPEARS TO BE A |
| | 300A SERVICE, YET PLANS INDICATE 200A'S. |
| | 230.70 , 215.5, 230.2 ETC |
| | |
| | 3) NOTE:NO, PLEASE SEE THE RISER DIAGRAM DOES NOT |
| | INDICATE ANY SERVICE ENTRANCE CONDUCTORS? PLEASE SEE |
| | THE CODE SECTIONS AS PREVIOUSLY NOTED WERE ADDED TO A |
| | NOTE #19, HOWEVER IT IS NOT PERMITTED TO PLACE CODE |
| | SECTIONS ON PLANS IN LIEU OF ACTUAL DETAIL OF DESIGN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE RISER DOES NOT INDICATE ANY SEC'S . PLEASE |
| | COMPLETE RISER. |
| | 310.15B6,310.16,240.4 ETC |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE:NO, SEE NOTE #2, FOR CLARIFICATION OF SERVICE |
| | MAIN EQUIPMENT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE INFORMATION FOR MAIN/PANEL/DISCONNECT ON |
| | RISER WHICH FEEDS TWO SUB PANELS. PLEASE SEE 230.70 AS |
| | THERE CAN BE NO MORE THAN 6 SPACES FOR EQUIPMENT AND NO |
| | MORE THAN 6 MAINS FOR SERVICE. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: OK. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK; HOWEVER SEE POSSIBLE NOTE UNDER 06081932 |
| | AS THE SAME RISER SHOULD BE NOTED UNDER THAT REVIEW. |
| | CABANA IS UNDER A SEPARATE PERMIT.. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE: NO, PLEASE SEE CIRCUITING WHICH HAS NOW BEEN |
| | ADDED TO PLANS WHICH DO NOT CORRELATE WITH THE PANEL |
| | SCHEDULE SUBMITTED. AS PREVIOUSLY NOTED, PLEASE ONLY |
| | INDICATE THE AREAS WHICH ARE BEING FED FROM THE |
| | CIRCUITS ON PANEL SCHEDULE. |
| | PLEASE SEE NOW PLANS INDICATE BATH ROOM GFI"S BEING FED |
| | FROM THE SMALL APPLIANCE CIRCUIT(S). |
| | PLEASE SEE SMALL APPLIANCE CIRCUITS FEEDING BEDROOM, |
| | HALLWAY, LIVING ROOM ETC. |
| | PLEASE SEE ONLY ONE SMALL APPLIANCE CIRCUIT SHOWN IN |
| | KITCHEN ETC. |
| | PLEASE KNOW IT WAS ONLY REQUESTED TO INDICATE ON THE |
| | PANEL SCHEDULE THESE AREAS/ROOMS. |
| | PLEASE SEE THE FOLLOWING SECTIONS FOR ITEMS NOT |
| | PERMITTED ON SMALL APPLIANCE OR BATHROOM CIRCUITS. |
| | 210.52B1, 210.52D, 210.11C1, 210.11C3, 220.16 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE PANEL SCHEDULE FOR ALL CIRCUITS TO THE |
| | ROOMS AND AREAS IN WHICH THEY FEED. CIRCUITS ARE TO BE |
| | SPECIFIC. IE: LIVING RM, KITCHEN LTS, ETC. |
| | 408.6. |
| | 106.1.2 |
| | ** IT IS KNOWN TO THIS OFFICE THAT THE CIRCUITING WILL |
| | BE REVISED AT A LATER DATE, HOWEVER THE MINIMUM IS |
| | REQUIRED AT THIS TIME. |
| | |
| | 15) NOTE: OK. |
| | |
| | 16) NOTE: OK. |
| | |
| | 17) NOTE:NO, PLEASE SEE THIS IS THE SAME NOTE, PLEASE |
| | SEE MISSING DISCONNECT AT THE CU. |
| | 440.11, 110.26 |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS ARE MISSING THE DISCONNECTS REQUIRED |
| | FOR THE A/C CU AND THE SPRINKLER PUMP/IRRIGATION. |
| | 440.11, 430.31 |
| | |
| | 18) NOTE: OK. |
| | |
| | 19) NOTE: OK. |
| | |
| | 20) NOTE: OK. |
| | |
| | 21) NOTE: OK. |
| | |
| | 22) NOTE: OK. |
| | |
| | 23) NOTE: OK. |
| | |
| | |
| | ** NEW NOTES ** |
| | |
| | 24) NOTE: PLEASE SEE RISER MENTIONS "RIGID" CONDUIT |
| | BEING INSTALLED, PLEASE VERIFY THIS AT THIS TIME, AS |
| | THIS TYPE OF CONDUIT FOR THIS INSTALLATION IS NOT |
| | USUAL. THIS DOES NOT VIOLATE ANY CODE, HOWEVER PLEASE |
| | KNOW IF INSTALLATION OF PVC CONDUIT IS USED INSTEAD |
| | WHICH IS OK, THEN AN EQUIPMENT GROUNDING CONDUCTOR |
| | WOULD BE REQUIRED TO CABANA AND PLANS WOULD BE REVISED |
| | TO INDICATE CONDUIT OTHER THAN "RIGID". |
| | THIS IS NOTED ONLY. |
| | |
| | 25) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) GIVEN |
| | ONLY AS A NOTICE AT THIS TIME AS SOME COMMENTS WERE |
| | INDEED REPEAT COMMENTS FROM PREVIOUS REVIEW. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-11-30 13:57:33 | FROM ZONING/INCOMING ON 11/29 |