| 2006-08-31 00:00:00 | ****** UNSAT ****** |
| | |
| | 1) NOTE; PLEASE SUBMIT AIC RATINGS FOR |
| | ALL EQUIPMENT. NOTE MENTIONS 22K FOR |
| | MAIN DISCONNECT, HOWEVER INFORMATION ON |
| | RISER DOES NOT SHOW A MAIN DISCONNECT. |
| | PLEASE ALSO INCLUDE ALL OTHER SERVICE |
| | EQUIPMENT RATINGS. |
| | 110.9 |
| | FBC 106.1.2 |
| | |
| | 2) NOTE; PLEASE CORRELATE PLANS AND |
| | RISER. RISER SHOWS WHAT APPEARS TO BE A |
| | 300A SERVICE, YET PLANS INDICATE 200A'S. |
| | |
| | 230.70 , 215.5, 230.2 ETC |
| | |
| | 3) NOTE: PLEASE SEE RISER DOES NOT |
| | INDICATEANY SEC'S . PLEASE COMPLETE |
| | RISER. |
| | 310.15B6,310.16,240.4 ETC |
| | |
| | 4) NOTE: PLEASE SEE RISER SHOWS 1/0'S |
| | FOR FEEDERS TO SUB PANEL, "A", YET THE |
| | MAIN BREAKER BEING SHOWN FEEDING THIS |
| | PANEL IS 200A'S. 1/0'S ARE NOT LARGE |
| | ENOUGH. |
| | 310.16, 240.4 |
| | |
| | 5) NOTE: PLEASE PROVIDE INFORMATION FOR |
| | MAIN/PANEL/DISCONNECT ON RISER WHICH |
| | FEEDS TWO SUB PANELS. PLEASE SEE 230.70 |
| | AS THERE CAN BE NO MORE THAN 6 SPACES |
| | FOR EQUIPMENT AND NO MORE THAN 6 MAINS |
| | FOR SERVICE. |
| | |
| | 6) NOTE: PLEASE INDICATE THE SIZE OF THE |
| | METER CAN BEING PROVIDED. |
| | 106.1.2 FBC |
| | |
| | 7) NOTE: PLEASE CORRELATE RISER AND |
| | PANELS, AS PANEL FOR CABANA IS BEING |
| | SHOWN ONE SIZE AND RISER SHOWS ANOTHER. |
| | 106.1.2 FBC |
| | |
| | 8) NOTE: PLEASE SEE LOADS SHOWN FOR A/C |
| | INDICATES COMPRESSOR LOAD FOR THE 10KW, |
| | WHERE THE AHU, IS THE LARGER OF THE TWO, |
| | THE CALCULATIONS SHOULD INDICATE THE |
| | AHU. |
| | 220.21., 220.31 |
| | |
| | 9) NOTE; PLEASE SEE MISSING GROUNDING |
| | ELECTRODE SYSTEM AT THE DETACHED |
| | BUILDING. |
| | 250.32, 250.50. |
| | |
| | 10) NOTE: ONCE RISER HAS BEEN CORRECTED |
| | FOR THE SIZE OF PANELS ETC AT CABANA, |
| | PLEASE BE SURE TO CLEARLY INDICATETHE |
| | MAIN DISCONNETC AT THE DEACHED BUILDING |
| | MEETING 225.31-225.39. |
| | PLEASE KNOW, SINCE PLANS FOR THE CABANA |
| | HAVE NOT BEEN SUBMITTED AT THIS TIME, |
| | THIS CAN NOT BE VERIFIED FOR CODE |
| | COMPLIANCE. |
| | |
| | 11) NOTE: PLEASE SUBMIT AND COMPLETE |
| | PLANS FOR CABANA IF PART OF THIS PERMIT APPLICATION |
| | ETC. PLEASE KNOW, NO REVIEW |
| | COULD BE DONE FOR CABANA , AND THERE MAY |
| | BE COMMENTS TO FOLLOW. |
| | 106.1.2 FBC, 2002 NEC. |
| | |
| | 12) NOTE: PLEASE SEE 422.11(E)3,AS THE |
| | OCP FOR THE WATER HEATER CAN NOT EXCEED |
| | 150%. PLEASE SEE 60A OCP IS BEING SHOWN |
| | ON A 5KW UNIT. |
| | PLEASE ADJUST. |
| | 106.1.2 |
| | |
| | 13) NOTE: PLEASE SEE CONDUCTOR SIZE |
| | BEING SHOWN ON PANEL SCHEDULE FOR RANGE |
| | DOES NOT CLEARLY INDICATE THE SIZE. |
| | SEEMS TO CONTAIN A MISPRINT. |
| | 310.16,240.4 |
| | |
| | 14) NOTE: PLEASE COMPLETE PANEL SCHEDULE |
| | FOR ALL CIRCUITS TO THE ROOMS AND AREAS |
| | IN WHICH THEY FEED. CIRCUITS ARE TO BE |
| | SPECIFIC. IE: LIVING RM, KITCHEN LTS, |
| | ETC. |
| | 408.6. |
| | 106.1.2 |
| | ** IT IS KNOWN TO THIE OFFICE THAT THE |
| | CIRCUITING WILL BE REVISED AT A LATER |
| | DATE, HOWEVER THE MINIMUM IS REQUIRED AT |
| | THIS TIME. |
| | |
| | 15) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 FOR 2' OF WALL SPACE OR MORE. |
| | |
| | 16) NOTE: PLEASE SEE NOTE #7 ON PLANS |
| | WHICH REFERENCES A CODE IN THE NEC, |
| | PLEASE KNOW, HOWEVER THIS MUST BE FROM |
| | AN OLDER NEC, AS THE CURRENT NFPA-70 IN |
| | EFFECT DOES NOT CORRELATE WITH THIS |
| | ARTICALE BEING REFERENCED. |
| | PLEASE ADJUST. |
| | |
| | 17) NOTE: PLEASE SEE PLANS ARE MISSING |
| | THE DISCONNECTS REQUIRED FOR THE A/C CU |
| | AND THE SPRINKLER PUMP/IRRIGATION. |
| | 440.11, 430.31 |
| | |
| | 18) NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING CONTROL AT MASTER BEDRM TO |
| | AREAS WITH GRADE LEVEL ACCESS. |
| | 210.70, LS 101 7.8 |
| | |
| | 19) NOTE: PLEASE KNOW, ALL FANS AND LT |
| | KITS WILL BE REQUIRED TO BE INSTALLED |
| | BEFORE FINALS, AS EGRESS LTS ARE |
| | REQUIRED. SINCE THE LIGHTING IS BEING |
| | SHOWN ON THE FANS, THESE WILL BE |
| | REQUIRED. |
| | ** PLEASE KNOW, IF USING A 1/2 SW RECEPT |
| | OR OTHER LIGHTING , THIS WOULD NOT BE |
| | REQUIRED. |
| | ** THIS NOTE IS FOR INFORMATIONAL |
| | PURPOSE ONLY. |
| | |
| | 20) NOTE: PLEASE SEE RISER, PLEASE |
| | CLARIFY THE "9" BEING SHOWN AS THE |
| | DESRIPTION OF THE CONDUIT?? |
| | IT IS UNCLEAR WHAT THIS IS? |
| | 106.1.2 |
| | |
| | 21) NOTE: PLEASE SEE PLANS INDICATE |
| | SCOPE OF WORK BEING LOCATED IN "PALM |
| | BEACH COUNTY" , WHEN SCOPE OF WORK AND |
| | THIS JOB LOCATION IS LOCATED IN THE |
| | "CITY OF WEST PALM BEACH". |
| | |
| | 22) NOTE: PLANS TO NOTE: SD'S TO BE |
| | INSTALLED PER NFPA-72 2002, 11.5.1.1, |
| | 11.8.3 |
| | |
| | 23) NOTE: PLEASE SEE PLANS ARE MISSIGN |
| | THE PRINTED NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR SAID PLANS. |
| | FBC 106.1.2 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |