Plan Review Notes
Plan Review Notes For Permit 06080547
Permit Number 06080547
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-26 00:00:00 
 1) SUBMIT DETAIL DRAWINGS SHOWING HOW
 THE NEW WINDOWS WILL BE INSTALLED AT THE
 SCREEN ENCLOSURRE. SHOW THE HEADDER
 DETAIL AND OPENING DIMENTION OF EACH
 WINDOW.THOSE WINDOWS WHICH ARE
 NON-IMPACT REQUIRES HURRICANE
 PROTECTION. PROVIDE A FLOOR LAYOUT OF
 THE BUILDING SHOWING THE LOCATION OF
 EACH WINDOW.
  
 2) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726