Plan Review Notes
Plan Review Notes For Permit 06080530
Permit Number 06080530
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-09-15 00:00:00*****DENIED*****
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIALS AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 3.)CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONDERS ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 4.) EXITS SHALL REMAIN CLEAR AND
 UNOBSTRUCTED.
  
 5.) NFPA 101, 2003 EDITION AND FLORIDA
 FIRE PREVENTION CODE, 2004 EDITION SHALL
 BE REFERENCED.
  
 6.) SINCE THE SCOPE OF THE PROPOSED WORK
 IS FOR BUILDING 2, PLEASE INDICATE THE
 LOCATION OF THIS BUILDING IN
 RELATIONSHIP TO OTHER BUILDING(S) ON THE
 PROPERTY.
  
 7.) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR SPRINKLER AND FIRE
 ALARM SYSTEM INSATLLATION OR REMODEL.
  
 8.) PLEASE INDICATE INTERIOR FINISH FOR
 WALLS AND CEILINGS.CLASS A OR B IS
 REQUIRED IN THE MEANS OF EGRESS AREAS.
  
 9.)PANIC HARDWARE IS REQUIRED ON EXIT
 DOORS SERVING AN OCCUPANT LOAD GREATER
 THAN ONE HUNDRED.
  
 10.) PLEASE INDICATE/DISPLAY/SHOW
 LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, PULL STATIONS, FIRE EXTINGUISHER
 FOR THE PROPOSED.
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722