Plan Review Notes
Plan Review Notes For Permit 06080501
Permit Number 06080501
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-09 00:00:00****UNSAT 2ND REVIEW ****
  
 1) NOTE: NO, PLEASE SEE REPSONE LETTER
 MENTIONS DESIGN WERE DESIGNED TO THE
 MOST RECENT ADOPTED CODES, HOWEVER
 PLEASE KNOW, THE CODES WHICH ARE
 RELEVANT TO DESIGN ARE REQUIRED ON PLANS
 FOR SCOPE OF WORK SHOWN ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE PLANS REFLECT
 THE FOLLOWING CODES.
 2004 FBC , 2002 NFPA-70, 2002 NFPA-72,
 AND 2003 NFPA-101.
  
 2) NOTE: OK.
  
 3) NOTE: NO?? PLEASE KNOW IT IS UNCLEAR
 WHAT IS BEING DONE WITH THE SERVICE AS
 SHOWN ON PLANS. IT WAS ORIGINAL THOUGHT
 THAT THE SERVICE SHOWN ON PREVIOUS PLANS
 WAS "EXISTING", HOWEVER PLANS INDICATE
 THIS SERVICE IS PROPOSED. PLEASE SEE
 RESPONSE LETTER MENTIONS THIS WAS
 ALREADY DONE UNDER OTHER PLANSAND
 PERMITS AND THE LTR MENTIONS THIS
 INFORMATION AND DOCUMENTATION WAS
 SUBMITTED, HOWEVER COULD NOT LCOATE ANY
 OF THIS IN PACKAGE.?
 IF THIS SERVICE IS NEW ON THE PERMIT AND
 SCOPE, PLEASE COMPLETE RISER WITH ALL
 CONDUIT SIZES FOR RISER AND CONDUIT FROM
 MAIN TO GUTTER, GUTTER TO METERS AND
 OTHER MAINS, ALONG WITH SIZES OF ALL NEW
 MAINS, METERS, AND CONDUCTOR SIZES.
 ALSO IF PERMIT IS NEW UNDER THIS SCOPE,
 PLEASE PROVIDE A LAYOUT OF THE ENTIRE
 BUILDING WHICH NEW SERVICE IS BEING
 INSTALLED. DOES THIS "BUILDING " CONTAIN
 ANY OTHER SERVICES? IF THE NEW SERVICE
 IS TAKING PLACE OF A PREVIOUS SERVICE,
 PLEASE INDICATE.
 NEED TO SHOW SERVICE ON A PLAN "OVER
 VIEW" INDICATING ALL CLEARENCES AS
 REQUIRED. 110.26
 PLEASE KNOW, IF THIS SERVICE AS SHOWN
 BACKS UP TO THE ALLEEY IN THE REAR OF
 THIS BUILDING, BOLLARDS WILL BE REQUIRED
 TO PROTECT THE SERVICE EQUIPMENT.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE COMPLETE LOAD
 CALCULATIONSFOR EXISTING SERVICE AND
 NEW LOADS BEING ADDED.
 NOTE ON PLANS MENTIONS THIS, HOWEVER
 CALCULATIONS COULD NOT BE LOCTAED.
 220,215.5,
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE NOTE BELOW WHICH
 MENTIONS"IMPORTANT" ETC.
 PLEASE SEE THAT TWO COMPLETE SETS WERE
 NOT SUBMITTED IN THE ORDER AS PREVIOUSLY
 REQUESTED IN NOTE BELOW.
 ***************************************
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
 ***************************************
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  