Plan Review Notes
Plan Review Notes For Permit 06080501
Permit Number 06080501
Review Stop G
Sequence Number 1
Notes
Date Text
2006-08-26 00:00:00DENIED;
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2.A UNION IS REQUIRED BETWEEN THE
 SHUTOFF VALVE AND THE EMERGENCY SHUTOFF
 VALVE FOR REPLACEMENT OR REPAIR OF
 VALVE.
 3.ADD A DRIP LEG TO YOUR ISOMETRIC AT
 KITCHEN EQUIPMENT SECTION408.4.
 4.LIST ALL GAS EQUIPMENT AND THE BTU'S
 OF EACH.
 5.NATURAL GAS REQUIREMENT NOTES;
 3.FPU GAS CO.PRESSURE IS 12"W.C.
 6.DELETE (OR FBC APPROVED EQUAL)
 PIPE MUST BE SIZED BY THE APPRO-
 PRIATE CHARTS IN CHAPTER 4 OF THE
 FBC FUEL GAS CODE.
 9.GAS PIPE TO BE INSTALLED PER FBC
 2004 FUEL GAS CODE NOT NFPA 54.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695