| Notes |
| Date |
Text |
| 2006-08-26 00:00:00 | DENIED; | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | 2.A UNION IS REQUIRED BETWEEN THE | | | SHUTOFF VALVE AND THE EMERGENCY SHUTOFF | | | VALVE FOR REPLACEMENT OR REPAIR OF | | | VALVE. | | | 3.ADD A DRIP LEG TO YOUR ISOMETRIC AT | | | KITCHEN EQUIPMENT SECTION408.4. | | | 4.LIST ALL GAS EQUIPMENT AND THE BTU'S | | | OF EACH. | | | 5.NATURAL GAS REQUIREMENT NOTES; | | | 3.FPU GAS CO.PRESSURE IS 12"W.C. | | | 6.DELETE (OR FBC APPROVED EQUAL) | | | PIPE MUST BE SIZED BY THE APPRO- | | | PRIATE CHARTS IN CHAPTER 4 OF THE | | | FBC FUEL GAS CODE. | | | 9.GAS PIPE TO BE INSTALLED PER FBC | | | 2004 FUEL GAS CODE NOT NFPA 54. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|