| 2007-04-10 16:54:00 | BUILDING REVISION SECOND CHECKLIST: | | | 1- THERE ARE NO REVISED PLANS SHOWING LOCATION OF NEW | | | SINGLE HUNG WINDOWS. PROVIDE REVISED PLANS. | | | | | | 2- STORM SHUTTERS DRAWINGS ARE INCOMPLETE. ONLY SHEET 1 | | | OF 19 WAS SUBMITTED. | | | | | | 3- ARCHITECT'S REVIEW STAMP DOESN'T STATE IF PRODUCT | | | APPROVAL WAS APPROVED OR NOT.REVIEW STAMP IS BLANK. | | | NOTHING IS MARKED STATINGWHAT ACTION WAS TAKENWITH | | | HIS REVIEW. | | | | | | 4- ON PREVIOUS CHECKLIST IT WAS REQUESTED TO PROVIDE | | | COMPLETE INFORMATION SHOWING HOW STORM PANELS ARE GOING | | | TO BE INSTALLED.THIS INFORMATION WAS NOT PROVIDED. | | | INDICATE IN DRAWINGS SPECIFIC ANCHOR TYPE AND SPACING | | | TO BE USED TO VERIFY COMPLIANCE WITH PROPOSED | | | INSTALLATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | 5- FLORIDA PRODUCT APPROVAL FL1435 HAS NOTHING TO DO | | | WITH NOA 06-0706.04. PROVIDE EITHERDADE COUNTY NOA | | | ALONE OR COMPLETE INFORMATION THAT WAS PROVIDED TO | | | OBTAIN FL1435 APPROVAL.ARCHITECT TO REVIEW AND | | | APPROVE SUCH PRODUCT APPROVAL AND USEORIGINAL STAMP | | | AS USED WITH PRODUCT APPROVAL FOR STORM SHUTTERS. COPY | | | OF REVIEW STAMP IS NOT ACCEPTABLE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|