| Plan Review Notes For Permit 06080496 |
| Permit Number |
06080496 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-06 00:00:00 | DENIED; | | | 1.AUTOMATIC CLOTHES WASHER BRANCH DRAIN | | | TO BE 3" FBC-2004 PLUMBING SEC. 406.3. | | | 2.THE A.C.M MUST DISCHARGE DOWN STREAM | | | OF THE BATHROOM GROUP. SEC 909.1. | | | 3.A CLEANOUT IS REQUIRED ON A.C.W. AT | | | 48" ABOVE FINISH FLOOR. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|