| Date |
Text |
| 2006-08-23 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE PLANS STATE "WORK TO |
| | COMPLY WITH APPLICABLE CODES". PLEASE |
| | KNOW, PLANS SHALL STATE THE CODES AND |
| | DESIGN SPECIFIC IN DESIGN. |
| | PLANS SHOULD REFLECT CODES FOR RELEVANT |
| | WORK IN SCOPE. |
| | FBC 2004, NFPA-70 2002 . (NEC). |
| | |
| | 2) NOTE: PLEASE SEE OTHER NOTE ON PLANS |
| | MENTIONS CIRCUITING WAS VERIFIED IN |
| | ORDER TO ADDED NEW FIXTURES WITH THE |
| | INCREASED WATTAGE, HOWEVER BASED ON THE |
| | NUMBE ROF FIXTURES SHOWN ON SOME |
| | CIRCUITS AND THE VOLTAGE OF SAID |
| | CIRCUITS NOT BEING SHOWN, PLEASE SEE |
| | CIRCUIT(S) WHICH APPEAR TO BE OVER |
| | LOADED. |
| | PLEASE SEE VOLTAGE SHOULD BE STATED FOR |
| | EEACH OF THE PANELS/SYSTEMS FOR EXISTING |
| | CIRCUITS. 120, 208, 277 ETC. |
| | PLEASE ALSO KNOW, ALL CONTINUOUS LOADS |
| | SHOULD BE VERIFIED FOR NEW LOADS. |
| | (3 OR MORE HRS). |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |