| Date |
Text |
| 2006-09-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | |
| | 1. BUILDING SHALL BE DESIGNED TO THE |
| | FBC-2004 CODE. PLEASE INDICATE ON PLANS. |
| | SECTION 106.1.1 |
| | |
| | 2. PROVIDE AN EXISTING FLOOR PLAN TO |
| | DETERMINE EXTENT OF ALTERATION. SECTION |
| | 106.1.1. |
| | |
| | 3. SHT A1.2 IN THE INSTALLATION OR |
| | REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| | SECTION 704.5. |
| | |
| | 4. SHT A2.1 A DRINKING FOUNTAIN IS |
| | REQUIRED PER TABLE 403.1. NO DRAINAGE OR |
| | WATER SUPPLY IS SHOWN TO THE DRINKING |
| | FOUNTAIN. PLEASE CLARIFY. |
| | |
| | 5. SHT A2.1 ACCESSIBILITY REQUIREMENTS. |
| | SHOW THE FOLLOWING: |
| | FOR W/C'S |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | FOR LAV'S |
| | A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | B. 11-4.19.5 FAUCETS |
| | |
| | 6. SHT A2.1 SHOWS A FREE STANDING |
| | DRINKING FOUNTAIN, AND A WALL HUNG |
| | DRINKING FOUNTAIN DETAIL. PLEASE |
| | INDICATE WHICH TYPE WILL BE INSTALLED. |
| | SECTION 106.1.1. IF THE WALL HUNG TYPE |
| | WILL BE USED, A FORWARD APPROACH CLEAR |
| | FLOOR SPACE IS REQUIRED. SECTION |
| | 11-4.15.5. ALSO SHOW PROVISIONS FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING AS REQUIRED BY SECTION |
| | 11-4.1.3(10)(A), IF THIS IS NOT A |
| | HIGH/LOW DRINKING FOUNTAIN. |
| | |
| | 7. SHT A4.1 SCUPPERS SHOWN ON SHT A5.1 |
| | ARE NOT SHOWN ON THE ELEVATIONS. PLEASE |
| | INDICATE THE SCUPPERS. SECTION 106.1.1. |
| | |
| | 8. SHT A5.1 SUBMIT CALCULATIONS FOR THE |
| | ROOF DRAINS PER SECTIONS 1106 & 1107 |
| | WITH ALL SUBSECTIONS. SIZE GUTTERS AND |
| | DOWNSPOUTS REQUIRED BY SECTION 1503.6 |
| | PER TABLES 1106.3 AND 1106.6. SHOW THE |
| | SQUARE FOOTAGE BEING DRAINED BY EACH |
| | DOWNSPOUT. SHOW ENTIRE SQUARE FOOTAGE |
| | BEING DRAINED AS WELL AS 1/2 AREA OF ALL |
| | VERTICAL WALLS, INCLUDING PARAPETS, IN |
| | THE CALCULATIONS. INDICATE SLOPE OF THE |
| | GUTTER AND INDICATE THE LOCATION OF THE |
| | HIGH SPOTS OF THE GUTTER. |
| | |
| | 9. SHT A5.1 SEPARATE PRIMARY AND |
| | SECONDARY ROOF DRAINS ARE REQUIRED ON |
| | THE LOWER ROOF. SUBMIT CALCULATIONS |
| | SHOWING THE SQUARE FOOTAGE OF THE ROOF |
| | AS WELL AS 1/2 AREA OF ALL VERTICAL |
| | WALLS INCLUDING PARAPETS. SHOW THE |
| | PRIMARY ROOF DRAINS. DETAIL SHOWN |
| | INDICATES EMERGENCY OVERFLOW SCUPPERS AS |
| | THE FLOW LEVEL IS 2" TO $' OFF THE ROOF. |
| | |
| | 10. SUBMIT A WATER RISER DIAGRAM. SHOW |
| | ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS, (IF REQUIRED BY SECTION 604.9 |
| | - (W/M'S, D/W'S, OR ICE MAKERS). ALSO |
| | SEE SECTION 606.1(4). SECTION |
| | 106.3.5.1.3. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |