| Plan Review Notes For Permit 06080439 |
| Permit Number |
06080439 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-20 00:00:00 | *** DENIED *** | | | 1) SEE ENERGY CAL'S. PAGE 6 AND | | | COMPLETE. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT, PER 2004 FBC | | | 13-600.3.ABC.2 | | | | | | 3) PLEASE PROVIDE OUTDOOR AIR AND | | | OUTDOOR AIR CALCULATIONS, PER 2004 FBC/M | | | 403.2 . | | | | | | 4) PLEASE SHOW SIZES OF SUPPLY AIR DUCTS | | | (FLEX) TO NEW ADDITION AND TO BATHROOMS | | | IN EXISTING. | | | | | | 5) PLEASE SEE HIGH LITED WALLS ON | | | MECHANICAL PLAN AS THEY ARE FIRE RATED | | | AND REQUIRE FIRE DAMPERS. | | | | | | 6) PLEASE SHOW A MANUFACTURE DETAIL FOR | | | FIRE DAMPERS ON PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|