| Date |
Text |
| 2006-08-27 00:00:00 | ***** UNSAT ***** |
| | |
| | 1) NOTE: PLEASE SEE THE SOIL BEARING |
| | REPORTS , FIELD REPORTS ARE IN FACT |
| | SEALED WITH A RAISED SEAL OVER |
| | SIGNATURES WHICH ARE PHOTO-COPIES OF |
| | ORIGINAL SIGNATURES. PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 AND |
| | FLORIDA STATUES 471.025, AS BOTHE OF |
| | THESE REQUIRE ALL SIGNATURES TO BE |
| | ORIGINAL. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT |
| | IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE SEE NOC WAS RECORDED ON |
| | 6/21/06 WHICH WAS RECORDED WITHOUT THE |
| | PCN/TAX FOLIO NUMBER ON SAID DOCUMNET. |
| | PLEASE ALSO KNOW FOR INFORMATION |
| | PRUPOSES, THE NOC WILL BECOME VOID IF |
| | WORK HAS NOT COMMENCED WITHIN 90 DAYS OF |
| | RECORDING SUCH NOC. PLEASE KNOW THE NOC |
| | IS ONLY REQUIRED BEFORE PICKING UP |
| | PERMIT. |
| | FS 713.13(2). |
| | |
| | 3) NOTE: PLEASE SEE ONLY ONE COPY OF THE |
| | FLORIDA ENERGY CODE CALCULATIONS WAS |
| | SUBMITTED. |
| | 2004 FBC CHAPTER 13 |
| | |
| | 4) NOTE: PLEASE INDICATE AND SHOW ALL |
| | ROOM AND AREA DESIGNATIONS ON PLANS. |
| | PLEASE COMPLETE ALL CIRCUITING ON PLANS |
| | AND PLEASE CORRELATE ALL CIRCUTING ON |
| | PLANS WITH THE PANEL SCHEDULE(S) |
| | SUBMITTED. PLEASE KNOW, CIRCUITS SHALL |
| | BE SPECIFIC TO AREAS/ROOMS ARE SHOWN ON |
| | PLANS. *GEN LTS AND GEN RECEPTS NEEDS TO |
| | BE MORE SPECIFIC* |
| | 408.4, 310.16, 240.4 |
| | |
| | 5) NOTE: PLEASE BE SURE PLANS REFLECT |
| | ALL THE CURRENT RELEVANT CODES SURRENTLY |
| | ADOPTED BY THE STATE OF FLORIDA. |
| | PLEASE SEE PLANS DO SHOW THE 2001 FBC IN |
| | SOME LOCATIONS. |
| | PLEASE SEE WE ARE CURRENTLY UNDER THE |
| | 2002 NFPA-70(NEC), 2002 NFPA-72, 2003 |
| | NFPA-101, 2004 FBC. |
| | 106.1 |
| | |
| | 6) NOTE: PLEASE CLARIFY RISER AS SHOWN. |
| | PLEASE SEE AN ADDITIONAL METER CAN IS |
| | BEING SHOWN FOR WHAT WOULD BE A NEW |
| | TENANT, HOWEVER THIS IS ONLY ONE TENANT |
| | AND ONLY ONE METER WIL BE PERMITTED |
| | UNLESS PROPER TENANT SEPARATION IS |
| | BUILT. |
| | PLEASE ALSO SEE RISER SHOWS A NEW MAIN |
| | DISCONNECT ON THE LINE SIDE OF THE FPL |
| | METERS. PLEASE SEE FPL SERVICE STANDARDS |
| | AS THE MAINS WOULD BE REQUIRD ON THE |
| | LOAD SIDE. |
| | PLEASE SEE RISER AS SHOWN MUST BE |
| | RE-DESIGNED. |
| | 90.4. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE MISSING GROUNDFING |
| | ELECTRODE SYSTEM PER 250.50. |
| | PLEASE COMPELTE, NEW FOOTER STEEL, COLD |
| | WATER PIPES ETC. |
| | |
| | 8) NOTE: PLEASE SEE LTS IN MANY |
| | LOCATIONS ARE BEING SHOWN AS A "J" WHERE |
| | IT APPEARS TO BE A 2X4 LAYIN TYOE |
| | FIXTURE. PLEASE CLARIFY IF THE "J" IS |
| | THE FIXTURE TYPE, THEN PLEASE INCLUDE |
| | ON THE FIXTURE SCHEDULE. PLEASE KNOW, |
| | LTS ARE REQUIRED IN ALL THESE LOCATIONS |
| | FOR MEANS OF EGREES ETC. |
| | NFPA-101 7.8 |
| | |
| | 9) NOTE: PLEASE SEE NOTE ABOVE #8, AS |
| | THE SAME IS SHOWN IN AHU CLOSETS. |
| | PLEASE SEE 210.70 |
| | PLEASE ALSO SEE MISSING RECEPTS FOR |
| | AHU'S, AND MISSING GFI FOR CU'S . |
| | 210.63, 210.87 |
| | |
| | 10) NOTE: PLEASE SEE MISSING DISCONNECTS |
| | FOR AHU'S , 440.11,110.26 |
| | |
| | 11) NOTE: PLEASE SEE MISSING SIGN |
| | CIRCUIT(S). 600.5, 220.3(B)(6) |
| | |
| | 10) NOTE: PLEASE SUBMIT AND SHOW |
| | COMPLETE LOAD CALCULATTIONS FOR |
| | COMMERCIAL BUILDINGS. 220.3,220.10, |
| | 220.11,220.13, ETC AND ALL CONTINUOUS |
| | LOADS PER 215.3, 230.42 ETC |
| | |
| | 11) NOTE: PLEASE SEE LAODS ON PANELS ARE |
| | SHOWING BOTH THE COND UNITS AND THE |
| | AHU'S. PLEASE SEE 220.11 |
| | |
| | ** PLEASE BE AWARE OF ANY COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |