| 2006-09-05 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06080439 |
| | ADD: 2825 AUSTRALIAN AV |
| | CONT: TURSO CONTRACTING CO |
| | TEL: (561)358-4246 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED.2004 EXISTING |
| | BUILDING CODE INDICATE THE LEVEL OF |
| | ALTERATIONS? |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | G) OCCUPANT LOAD |
| | H) FLOOD ZONE |
| | I) FLOOD ELEVATION |
| | |
| | 3) SHEET A1.2 NOTE# 9 INDICATES GLAZING |
| | TO MEET THE REQUIREMENTS OF FBC 2001 |
| | PLEASE CORRECT TO THE CURRENT CODE FBC |
| | 2004. |
| | |
| | 4) SHEET A1.1 PLEASE PROVIDE ELEVATIONS |
| | FOR THE SITE PLAN.11-4.3.7 SLOPE. |
| | AN ACCESSIBLE ROUTE WITH A RUNNING SLOPE |
| | GREATER THAN 1:20 IS A RAMP AND SHALL |
| | COMPLY WITH SECTION 11-4.8 . NOWHERE |
| | SHALL THE CROSS SLOPE OF AN ACCESSIBLE |
| | ROUTE EXCEED 1:50. |
| | |
| | 5) 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 6) SHEET A8.1 INDICATES 2 SECTIONS |
| | 1-2/S1 THERE ARE NO STRUCTURAL SHEETS, |
| | ONLY "A" SHEETS. |
| | |
| | 7) SHEET A8.2 SAME ISSUE PLAN DETAILS |
| | INDICATE STRUCTURAL SHEETS. |
| | |
| | 8) A8.3 DETAILS OF STEEL COLUMN AND |
| | 8"X30" STEEL EMBED PLATE DOESN'T |
| | INDICATE THE TYPE OF WELDNOR SIZE OF |
| | WELD. 106.1.2* ADDITIONAL INFO REQUIRED. |
| | |
| | 9) SHEET A8.3 DETAIL# 2&4 INDICATES A |
| | STEEL PARAPET BUT NO ATTACHMENT METHOD |
| | IS PROVIDED?106.1.2* ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 10) A8.3 STEEL STUD PARAPET DETAILS ARE |
| | MISSING DETAILS SUCH AS : |
| | 10A) WEATHER RESISTANT BARRIER 2510.6 |
| | 10B) TYPE OF WIRE LATH, WEIGHT OF WIRE |
| | LATH, AND ATTACHMENT, ASTM C1063. |
| | |
| | 11) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 12) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 13) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 1) TAMKO BUR ROOF SYSTEMS |
| | ONLY THE FIRST 4 SHEETS OF THIS REPORT |
| | WERE SUBMITTED. NO SUBSYSTEM WAS |
| | SUBMITTED OR HIGHLIGHTED. NOTE SYSTEMS |
| | LIMITATION# 7. FOR THIS PROJECT THERE |
| | WILL NEED TO HAVE 3 SEPERATE SUBSYSTEMS |
| | ONE FOR CONCRETE TWIN TEES WITH |
| | INSULATED DECK, ONE FOR SSTEEL DECK WITH |
| | INSULATION AND A STEEL DECK NO |
| | INSULATION. |
| | THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN |
| | |
| | ROOF HEIGHT. |
| | |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF |
| | PITCH. |
| | |
| | _X__ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED. |
| | |
| | _X__ THE SYSTEM PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE _3__ . |
| | |
| | __X_ THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | ___THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PROVISO: |
| | 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSELY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORIC SURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. |
| | ACCORDINGLY, DEVELOPERS, CONTRACTORS, |
| | AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| | ITEMS, ON EXISTING PROPERTIES RESULTING |
| | IN A DECREASE IN EXCESS OF 800SQ FT OF |
| | PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| | AS A PERMIT CONDITION, PROVIDE A |
| | PROFESSIONALLY PREPARED DRAINAGE PLAN |
| | CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| | WINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |