| 2006-10-17 10:22:49 | DENIED: | | | 1.PERMIT APPLICATION INDICATES DIESEL GENERATOR | | | WHEREAS THE MANFUACTURER'S SUBMITTAL INDICATES NATURAL | | | GAS OR LP WAS THIS SUBMITTED IN ERROR.SUBMITTAL | | | PACKAGE ALSO INCLUDES A DIESEL GENERATOR.PLEASE | | | CORRELATE. | | | | | | 2.PLEASE COMPLETE THE "STANDARD FEATURES AND | | | ACCESSORIES SHEET" AS TO WHAT IS TO BE INSTALLED. | | | | | | 3.PLAN SHEET E2 INDICATES THE GENERATOR EXHAUST TO | | | OPEN AIR AT THE ROOF OF COVERED PARKING.PLEASE | | | PROVIDE THE FOLLOWING INFORMATION: | | | A) WHAT TYPE OF MATERIAL IS THE ROOF, I.E. | | | CONCRETE, CANVAS, ETC. | | | B) IS THIS A PITCHED OR FLAT ROOF,COMBUSTIBLE OR | | | NON-COMBUSTIBLE? | | | C) WILL THE EXHAUST PIPING EXTEND ABOVE THE ROOF? | | | HOW FAR? | | | D) PLEASE SUBMIT MANUFACTURE DETAIL FOR EXTENDING | | | THE MUFFLER EXHAUST. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected] |
|