2006-10-17 10:22:49DENIED:
 1.PERMIT APPLICATION INDICATES DIESEL GENERATOR
 WHEREAS THE MANFUACTURER'S SUBMITTAL INDICATES NATURAL
 GAS OR LP WAS THIS SUBMITTED IN ERROR.SUBMITTAL
 PACKAGE ALSO INCLUDES A DIESEL GENERATOR.PLEASE
 CORRELATE.
  
 2.PLEASE COMPLETE THE "STANDARD FEATURES AND
 ACCESSORIES SHEET" AS TO WHAT IS TO BE INSTALLED.
  
 3.PLAN SHEET E2 INDICATES THE GENERATOR EXHAUST TO
 OPEN AIR AT THE ROOF OF COVERED PARKING.PLEASE
 PROVIDE THE FOLLOWING INFORMATION:
 A) WHAT TYPE OF MATERIAL IS THE ROOF, I.E.
 CONCRETE, CANVAS, ETC.
 B) IS THIS A PITCHED OR FLAT ROOF,COMBUSTIBLE OR
 NON-COMBUSTIBLE?
 C) WILL THE EXHAUST PIPING EXTEND ABOVE THE ROOF?
 HOW FAR?
 D) PLEASE SUBMIT MANUFACTURE DETAIL FOR EXTENDING
 THE MUFFLER EXHAUST.
  